Maintenance instructions

To ensure operational safety, the electrical system must undergo regular repeat tests by
a qualified electrician in accordance with the German Ordinance on Industrial Safety and
Health (BetriebsSichV). Tighten all screw connections of the HTEs as well as screw
connection points of the PE terminal. A torque of 2 Nm must be applied. Tighten the
screw connections of the circuit breakers with a torque of 2.8 Nm. Check the circuit
breakers for function according to the manufacturer's specifications. Check the housing
seal for possible damage and, if necessary, replace it with a new seal with the same
sealing area.
For final sealing of the housing, moisten the four sealing shells again with the separately
available assembly agent POWERSIL
Enclosure
All maintenance work must be carried out by qualified personnel. All applicable installa-
tion and accident prevention regulations must be observed. Non-observance can result
in damage to the equipment and danger to life and limb.
MAINTENANCE
24
Paste AP (article no. 492 590 01).
®