Herunterladen Inhalt Inhalt Diese Seite drucken

Busbar Tap-Off Unit - System Bd2 - 250/400/530 A, Without Cover Disconnector - janitza AKM 806 Benutzerhandbuch

Vorschau ausblenden Andere Handbücher für AKM 806:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

www.janitza.de
4.2
Busbar tap-off unit –
System BD2 - 250/400/530 A,
without cover disconnector
INFORMATION
The following steps show the assembly of the bus-
bar tap-off unit (system BD2 - 250/400/530 A vari-
ants, without cover disconnector), regardless of the
equipment/installation. Please note, as already de-
scribed under „Installation and equipment options
– schematic diagrams" auf S. 68, that the equip-
ment of your busbar tap-off unit and thus the infor-
mation on the mounting of components and cabling
may differ from the following figures!
The 250 A, 400 A and 530 A versions of the AKM
have no cover disconnector. The assembly and dis-
assembly of the busbar tap-off unit (AKM) without
cover disconnector is only possible when the cover
is open.
A finger-safe design provides protection against
contact.
For the AKM versions with switching elements (fuse
switch or circuit breaker) the cover opens only when
the switching element is switched off (interlock)!
Safety load switch
(FS)
Circuit breaker,
rotary actuator (LSD)
Circuit breaker,
motor actuator (LSM)
Fig. 1: AKM with switching elements
1. Use a hexagon socket wrench or other suitable
tool to open the busbar tap-off unit (AKM).
2
Fig. 2: Open the AKM (1, 2, 3)
INFORMATION
Check the required space before installing
the AKM. Tap-off units must not be placed at
connection points over terminal blocks! The space
requirements of the AKM must be taken into
account already during the project planning stage!
Please also observe the further assembly and
installation instructions of the busbar system
manufacturer.
2. The 250/400/530 A versions of the AKM are
fixed to the busbar with a mounting aid that is
included.
Plug the mounting aid (anti-twist protection -
prevents incorrect positioning of the AKM) onto
the tap-off site of the busbar system. Please
note that depending on the national regulations
for electrical installations, mounting the tap-off
units while live might or might not be permitted.
In the case of live, switch off the voltage and
protect the busbar circuit against being swit-
ched on again in accordance with local regula-
tions (see warning symbol).
Fig. 3: Attach the mounting aid
Busbar tap-off unit
1
Depending on the AKM:
4x or 6x 10 mm (8 Nm)
3
73

Werbung

Kapitel

Inhaltsverzeichnis
loading