setting the input signal (inpuT)
Select the input signal for the set-point value in the INPUT menu
option. (4 ... 20 mA; 0 ... 20 mA; 0 ... 10 V or 0 ... 5 V).
process level (values are displayed)
Press for approx. 3 s
MENU
setting level
EXIT
Fig. 17: Operating structure INPUT; setting the input signal
30
INPUT
ENTER
X.TUNE
ADD.FUNCTION
Select the input
signal
4‑20 mA
0‑20 mA
0‑10 V
0‑5 V
EXIT
English
automatic adjustment of the positioner to the
operating conditions (X.Tune)
Warning!
danger due to the valve position changing when the X:TUNE
function is run!
When the X.TUNE function is run under operating pressure, there
is an acute risk of injury.
▶ Never run X.TUNE while the process is running!
▶ Secure system against unintentional activation!
note!
an incorrect supply pressure or incorrectly connected
operating medium pressure may cause the controller to be
wrongly adjusted!
▶ Run X.TUNE in each case at the supply pressure available in
subsequent operation (= pneumatic auxiliary power).
• Run the X.TUNE function preferably without operating medium
SELEC
pressure to exclude interference due to flow forces.
The following functions are actuated automatically:
• Adjustment of the sensor signal to the (physical) stroke of the
actuator used.
• Determination of parameters of the PWM signals to control
the solenoid valves integrated in type 8615500120-000 /
8615500130-000.
Type 8615500120-000 / 8615500130-000
Start-up