Info and menu parameters
SCH
LAYERED
ARRANGE-
MENT
SCH00
RETURN
FLOW
SWITCH
SCH01
DIFF.
RETURN
SWITCH
SCH02
TU SENSOR
TYPE
SCH03
TPR SENSOR
TYPE
SCH04
FIXED VALUE
TANK TU1
LEG
THERMAL
DISINFEC-
TION
LEG00
THERMAL
DISINFEC-
TION
LEG01
TEMP
TERM.DISIN-
FECTION
LEG02
HOLD TIME
TEMP.THE.DI
S
LEG03
TEMP.RISE
TSET
THM.DIS
08/2020 Item no. 215790 EA no. 1321
Adjuster is visible if RETURN FLOW SWITCH SCH00 (05:110) is not set to 0.
Option: Return flow switch (see above for basic
parameters)
Switch-off
Switch-off difference between the
boost for
buffer at bottom TUx and return
return layered
temperature of the heat exchanger
on the primary side TPR. TPR > T1U
arrangement
SRD TOP
+ SRD top = USR OFF (return is
charged in the middle section of
the tank)
n
TU tank
0: NTC 5K
bottom
n
1: PT 1000
sensor selec-
tion, sensor
type
n
TPR PWT pri-
0: NTC 5K
mary return
n
1: PT 1000
sensor selec-
tion, sensor
type
Substitute
Fixed value for the tank sensor at
value for tank
bottom if it is not possible to
sensor at
install a sensor. If a sensor is con-
bottom
nected, this value must be 120 °C.
Adjuster is visible if THERMAL DISINFECTION LEG00 (05:014) is not set to 0.
Thermal disinfection function (see above for basic
parameters)
Setpoint for
(legionella protection). Applies
thermal disin-
while a thermal disinfection has
fection
been activated.
Min. hold time
This adjuster defines how long the
for thermal
setpoint for thermal disinfection is
disinfection
maintained for legionella protec-
setpoint tem-
tion to be completed successfully.
perature
Boost for
Boost for the domestic hot water
thermal disin-
setpoint while thermal disinfection
fection
is in progress. To account for the
thermal losses in the system so
that the temperature 05:004
LegioSet can also be reached at
the reference sensor.
on/off
5...40
0...1
0...1
0...120
0...2
60...80
0...480
0...30
Operating instructions
ES 5941
off
0
05:110
K
25
05:105
-
25
28:023
-
25
28:028
°C
0
28:083
-
0
05:014
°C
0
05:004
min
0
05:043
K
25
36:024
31