General
Maximum Ambient Temperature
Minimum Ambient Temperature
Maximum Humidity
Electrical
Supply Voltage
Rated Input Current
Water Ingress Protection
Protection Against Electric Shock
Pollution Degree
Rated Impulse Voltage
Performance
Factory pre-set temperature
Factory pre-set temperature range
Programmable temperature range
For Type 3 installations, the supply conditions specified in the TMV3 Requirements manual take
precedence over the operating parameters which follow.
Water Supply
Supply connection
Minimum dynamic pressure
Maximum dynamic pressure
Maximum static pressure
Supply pressure differential
Minimum recommended differential
between hot supply and outlet temp
(consistent with HSE Guidelines)
Hot supply temp
Cold supply temp
Maximum disinfection temperature
1424780-ML2-A

Specification

40°C
1°C
95% rH
100 - 240 V 50/60 Hz
1 A
IP X4
Class II (double insulated)
2
2.5 kV
39°C
37°C - 41°C
33°C - 45°C (Full cold can be selected during
programming)
G 3/8 Female Thread
100 kPa (1.0 bar)
500 kPa (5.0 bar)
1000 kPa (10.0 bar)
Equal pressure recommended - inlet pressures
must be stable for optimum performance.
7°C
55°C - 65°C (60°C - 65°C Recommended)
1°C - 25°C
80°C
14
PSU
PSU
Valve
40°C
1°C
95% rH
Valve
12 V DC
2.0 A
IP X4
Class III (SELV)
2
18 V