Technical Data
Time circuit
Time ranges:
Time setting:
Recovery time:
Repeat accuracy:
Voltage influence:
Temperature influence:
Input
Nominal voltage U
:
N
Voltage range
AC:
DC:
Release voltage A1 - A2:
Release voltage A3 - A2:
Control current B1:
Min. operate / off time
of the control contact B1(+)
AC 50 Hz:
DC:
Release voltage (B1-A2)
AC 50 Hz:
DC:
Nom. consumption AC 24 V: Approx. 1 VA
Nom. consumption AC 230 V: Approx. 7.5 VA
Nom. consumption DC 24 V: Approx. 0.5 W
Nominal frequency:
Frequency range:
Output
Contacts
RK 7817.81:
RK 7817.82:
RK 7817.32:
Contact material:
Measured nominal voltage:
Thermal current I
:
th
Switching capacity
according to AC 15
NO contact:
NC contact:
Electrical life:
Mechanical life:
Permissible switching frequency
(without / at load):
Short circuit strength
max. fuse rating:
8 time ranges in one unit, settable
via rotational switch.
0.02*
... 1 s
0.3 ... 30 min
)
0.06*
)
... 6 s
3 ... 300 min
0.3 ... 30 s
0.3 ... 30 h
0.03 ... 3 min
3 ... 300 h
*
)
0.08 s bei Funktion AV und IE
Infinite, 1:100 on relative scale
< 100 ms
≤ 0.8 % of set time delay + 20 ms
≤ 1 %
≤ 2 % at range 0 ... +60°C
≤ 5 % at range -20 ... 0°C
AC/DC 24 V
+ AC 230 V
or
1)
2)
AC/DC 24 V
+ AC 110 ... 127 V
1)
AC/DC 24 V
or
1)
DC 12 V
1)
at terminals A3-A2
1)
at terminals A1-A2
2)
0.8 ... 1.1 U
N
0.9 ... 1.25 U
N
AC 50 Hz approx. 30 V
DC approx. 4 V
Input resistance approx. 150 kΩ
in series with diode
Approx. 25 ms / approx. 60 ms
Approx. 15 ms / approx. 60 ms
Approx. 5 V
Approx. 4 V
50 Hz / 60 Hz
± 5 %
1 changeover contact delayed (15-16-18)
2 changeover contact delayed
(15-16-18), (25-26-28)
1 changeover contact delayed (15-16-18)
1 changeover contact as instantaneous
contact (21-22-24)
AgNi
AC 250 V
4 A
2 A / AC 230 V
IEC/EN 60947-5-1
1 A / AC 230 V
IEC/EN 60947-5-1
> 1 x 10
switch. cycl. IEC/EN 60947-5-1
5
> 1 x 10
switching cycles
7
7200 / 360 switching cycles / h
4 A gG / gL
IEC/EN 60947-5-1
Technical Data
General Data
Nominal operating mode:
Temperature range
Operation:
Storage:
Relative air humidity:
Altitude:
Clearance and creepage distance
Rated impulse voltage /
pollution degree:
Overvoltage category:
Insulation test voltage,
type test:
EMC
Electrostatic discharge (ESD):
HF irradiation
80 MHz ... 2,7 GHz:
Fast transients:
Surge voltage
between
wires for power supply:
between wire and ground:
or
2)
HF-wire guided:
Interference suppression:
Degree of protection
Housing:
Terminals:
Enclosure:
Vibration resistance:
Climate resistance:
Terminal designation:
Wire connection:
Fixed screw terminals
Cross section:
Stripping length:
Wire fixing:
Plug-in screw terminals
Cross section:
Stripping length:
Wire fixing:
Plug-in cage clamp terminals
Cross section:
Stripping length:
Wire fixing:
Fixing torque:
Mounting:
Weight:
Dimensions
Width x height x depth:
RK 7817:
RK 7817 PC:
RK 7817 PS:
15
Continuous operation
- 20 ... + 60 °C
- 25 ... + 70 °C
93 % at 40 °C
< 2000 m
4 kV / 2 (basis insulation)
IEC 60664-1
III
2,5 kV; 1 min
8 kV (air)
IEC/EN 61000-4-2
10 V/m
IEC/EN 61000-4-3
4 kV
IEC/EN 61000-4-4
2 kV
IEC/EN 61000-4-5
4 kV
IEC/EN 61000-4-5
10 V
IEC/EN 61000-4-6
Limit value class B
IP 40
IEC/EN 60529
IP 20
IEC/EN 60529
Thermoplastic with VO behaviour
according to UL Subject 94
Amplitude 0.35 mm
Frequency 10 ... 55 Hz, IEC/EN 60068-2-6
20 / 060 / 04
IEC/EN 60068-1
EN 50005
DIN 46228-1/-2/-3/-4
0.34 ... 2.5 mm² (AWG 22 - 14) solid or
0.34 ... 2.5 mm² (AWG 22 - 14)
stranded wire with and without ferrules
7 mm
Captive slotted screw / M2.5
0.2 ... 2.5 mm² (AWG 24 - 12) solid or
0.2 ... 2.5 mm² (AWG 24 - 12)
stranded wire with and without ferrules
7 mm
Captive slotted screw / M2.5
0.2 ... 2.5 mm² (AWG 24 - 12) solid or
0.25 ... 2.5 mm² (AWG 24 - 12)
stranded wire with and without ferrules
10 mm
Cage clamp terminal
0.5 Nm
EN 60999-1
DIN-rail
IEC/EN 60715
70 g
17.5 x 90 x 66 mm
17.5 x 121 x 66 mm
17.5 x 107 x 66 mm
RK 7817 / 23.12.20 en / 336A
EN 55011