Herunterladen Diese Seite drucken

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Figure 1a: M201E-240 (-KO)
Surface Mount Output Module
with 240V Relay Contacts
Figure 1c: M201E-240-DIN Din Rail Mounted
Output Module with 240V Relay Contacts.
TO MOUNT, LOCATE LUG OVER TOP
OF RAIL AND ROTATE THE MODULE
DOWN TO CLIP INTO PLACE.
TO REMOVE, PUSH UPWARDS, AND
ROTATE TOP OF MODULE AWAY
FROM RAIL.
Figure 2: Module Wiring
NOTE: Wiring is the same for M201E-240 (-KO) and M201E-240-DIN
Relay 1, N/O
7
Relay 2, N/C
8
Ground
9
Ground
10
Relay 2, N/C
11
Relay 1, N/O
12
8 9
6 7
5
4
3
2
1
0
TENS
ROTARY DECADE ADDRESS SWITCHES
Notes:
1. If short circuit isolation is not required, then the loop output should be wired
to terminal 5 rather than terminal 2. Terminal 5 is internally connected
directly to terminal 4.
2. In order to meet the requirements of European Safety Standards, ensure
that all cables carrying voltages in excess of 48V are suitably fused.
M201E-240:
0786
M201E-240-KO: DOP-IOD042
17
M201E-240-DIN: DOP-IOD043
EN54-17: 2005, EN54-18: 2005
D200-93-01
M201E-240, M201E-240-KO
INSTALLATION INSTRUCTIONS FOR MAINS
SWITCHING OUTPUT MODULES
Figure 1b Mounting
LOOP CABLE SCREEN TERMINAL
Loop -, Out
1
Loop +, Out - See Note 1
2
Loop -, In
3
Loop +, In
4
Loop +, Out - See Note 1
5
T6 - Not Connected
6
8 9
6 7
10
11
5
4
12
3
13
2
14
1
15
0
UNITS
Honeywell Products and Solutions Sàrl
DOP-IOD041
(Trading as System Sensor Europe)
Zone d'activités La Pièce 16
CH-1180 ROLLE, Switzerland
Pittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy
M201E-240-DIN
AND
This manual is intended as a quick reference installation guide. Please refer
to the control panel manufacturers installation manual for detailed system
information.
The installation must be carried out by expert personnel, that is, a person with
education or experience to identify hazards and take appropriate actions to
reduce the risk of injury to themselves and others.
GENERAL INFORMATION
The M200+ series of modules are a family of microprocessor controlled
interface devices permitting the monitoring and/or control of auxiliary devices.
The M201E-240, M201E-240-KO and M201E-240-DIN are output modules,
providing 250VAC 5A rated voltage free contacts, both normally open and
normally closed.
S
PECIFICATIONS
O perating Voltage Range: see S00-7200
LED Cutoff Voltage: 19.5 VDC (M201E-240-KO 17.5VDC)
Maximum Standby Current (µA): 275µA - No Communication
445µA - Communication LED blink enabled - 5 secs
375µA - Read 16 sec. LED blink 8 sec
Fault Current:
8.8 mA (Yellow LED illuminated)
Coil Activation/Deactivation Current: 76mA Maximum for 12mS
Relay Contact Rating:
5A, at 30VDC, 5A at 250VAC
Isolator Features:
see S00-7200
Operating Temperature: -20°C to 60°C
Humidity:
5% to 95% Relative Humidity
Dimensions M201E-240 and M201E-240-KO:
Dimensions M201E-240-DIN: 127 mm (H) x 76 mm (W) x 48 mm (D)
(Including terminals)
Weight M201E-240 and M201E-240-KO: 195 g
Weight M201E-240-DIN: 140 g
Maximum Wire Gauge 1.5mm² - M201E-240 (-KO), 2.5 mm² - (-DIN)
I
NSTALLATION
Note: These modules must only be connected to control panels using
compatible proprietary analogue addressable communication protocols
for monitoring and control.
Disconnect loop power before installing modules or sensors.
High voltages may be present on terminals 7 to 12.
M201E-240 and M201E-240 -KO
1.
The M201E-240 (-KO) includes a custom low profile surface-mounting
box with several options for fixing centres. To access all fixing points, and
the rear cable entry knock out, the circuit board must be removed. It is
held in place by two screws through the circuit board. Ensure that these
screws are replaced when refitting the circuit board.
2.
If rear cable entry is not required, the box has several cover drill points
permitting the entry of cables using suitable glands.
3.
Wiring to the M201E-240 (-KO) is made via two 6 way terminal strips on
the module circuit board, capable of supporting conductors up to 1.5mm².
See figure 2 for connections.
4.
An earthing terminal is provided in the surface mount box for connection
of the loop cable screen, if used, to ensure continuity. See figure 1a.
M201E-240-DIN
1.
M201E-240-DIN mounts onto standard 35 mm x 7.5 mm "Top Hat" DIN
rail. It must be mounted in a suitable cabinet meeting the applicable
safety standards.
2.
Wiring to the M201E-240-DIN is via plug in type terminals capable of
supporting conductors up to 2.5 mm². See figure 2 for connections.
Ensure that the correct terminals are used for the loop and switched
voltage as damage may result from incorrect usage.
For both modules, the address is selected by means of rotary decade address
switches (see figure 2), accessed at the front of the module. A screwdriver
should be used to rotate the wheels to select the desired address. (Note: The
number of addresses available will be dependent on panel capability, check
the panel documentation for information on this.)
Short Circuit Isolators
All M200+ series modules are provided with short circuit monitoring and
isolators on the intelligent loop. If required the isolators may be wired out of
the loop to facilitate the use of the modules on high current loaded loops, for
example if sounders are used. To achieve this, the loop out positive should be
wired to terminal 5 rather than terminal 2.
E N G L I S H
134 mm (H) x 139 mm (W) x 40 mm (D)
CAUTION
WARNING
I56-1768-017

Werbung

loading

Inhaltszusammenfassung für System Sensor M201E-240

  • Seite 1 Figure 2: Module Wiring Wiring to the M201E-240 (-KO) is made via two 6 way terminal strips on NOTE: Wiring is the same for M201E-240 (-KO) and M201E-240-DIN the module circuit board, capable of supporting conductors up to 1.5mm².
  • Seite 2 134 mm (H) x 139 mm (L) x 40 mm (P) Figura 1c: Modulo di uscita montato su binario Din Dimensioni del modello M201E-240-DIN : 127 mm (H) x 76 mm (L) x 48 mm (P) M201E-240-DIN con contatti di relè da 240 V.
  • Seite 3 M201E-240-DIN SALIDA + DEL LAZO - VER NOTA 1 1. El M201E-240-DIN se monta en rieles estándar DIN "Top Hat" de 35 mm x T6 - NO CONECTADO 7,5 mm. Debe ir montado en una cabina que cumpla todas las normativas aplicables sobre seguridad.
  • Seite 4 5% bis 95% Rel. Luftfeuchte Abbildung 1c: M201E-240-DIN Steuermodul mit Relais Abmessungen M201E-240(-KO): 134 mm(H) x 139 mm(B) x 40 mm(T) Abmessungen M201E-240-DIN: 127 mm(H) x 76 mm(B) x 48 mm(T), inkl. für Netzspannung zur Montage auf C-Hutschiene Klemmen Gewicht M201E-240(-KO): 195 g Gewicht M201E-240-DIN: 140 g Max.

Diese Anleitung auch für:

M201e-240-koM201e-240-din