10
Mounting and Connection Instructions Mains/charger unit 12 V DC / 18 Ah
8.
Start-up
L
Mains
110 V AC/
PE
230 V AC
N
Fault "S"
Mains "N"
red
Accum.
+
black
-
1. - Apply mains power
Check for 13.8 V output voltage
Output S: +12 V DC
Output N: +12 V DC
- Disconnect mains power
2. - Connect accumulator (observe polarity)
- Apply mains power
Output S: 0 V
Output N: +12 V DC
3. - Disconnect mains power
Check that the accum. continues to supply voltage
and current to the output load (ST1/2 and 3).
Output S:
a) +12 V DC: Accum. voltage low (<11.5 V)
b) 0 V:
Output N: 0 V
4. - Reconnect mains power
Output S: 0 V
Output N: +12 V DC
F1 Mains
T2A HRC
F1
F2
S
F2 12 V DC
+
T1,6A
-
N
F3 Accum.
F1,6A
+
-
F3
LED
LED
red
green
Action
fault: no accumulator
mains present
no fault
mains present
Accum. voltage o.k. (>11.5 V)
mains not present
no fault
mains present
LED red
(Fault)
1sec.
1
sec
.
1
sec
OFF: Accum. fully charged
or
Flashes: Accum. charging
1 sec.
1
sec
.
1
sec
3
sec
.
OFF: Accum. fully charged
or
Flashes: Accum. charging
1 sec.
1
sec
.
1
sec
LED green
(Mains)
ON
.
ON
.
OFF
ON
.