Fitting the LED tubes
Only use LED tubes that have been certified for these light
fittings, see Technical data and type label!
The LED tubes (G5) is to be inserted to its stop into the marked holders
so that both pins on either side of the lamp engage in the holder. Only the
holders on this side are wired with connecting wires.
Insert the cable entries of the LED - tubes into the socket use it in an
opposite side.
The lamp is to be inserted to its stop into both holders, so that both pins
on either side of the lamp engage in the holder.
Then turn the lamp to its lock-in position, see fig. 8 and fig. 9.
If the LED tubes are inserted with swapped ends, there is no function.
Observe the emission direction of the LED tubes.
Attention! Lamp exchange must be carried out while energy is
switched off.
Option: automatic double-pole switch while opening the protective
bowl.
5.

Taking into operation

– Prior to operation, check the light fitting for its proper functioning and
installation in compliance with these operating instructions and other
applicable regulations!
– Only carry out insulation measurements between PE and the external
conductor L1(L,L2,L3) as well as between PE and N!
- measuring voltage: max. 1 kV AC/DC
- measuring current: max. 10 mA
Only operate the light fitting with complete closed protective bowl.
6.

Maintenance

Observe the national regulations applicable to the maintenance,
servicing and test of electrical apparatus as well as the general rules
of engineering (e.g. EN/IEC 60079-17)!
The required maintenance intervals are set according to their application
and should therefore be determined depending on the conditions of use.
Servicing
When servicing, in particular those components that affect the type of
protection, will have to be checked, e. g.:
– Housing and protective bowl for any cracks or damages.
– Gaskets for their perfect condition.
– Terminals and blanking plugs for their firm fit.
– Because of the risk of an electrostatic charge, the light fitting shall only
be cleaned with a damp cloth or sponge!
Only use customary household washing-up liquid diluted in water as
specified! The water temperature may be max. 50 ºC. After that, rinse
with clear water to prevent the risk of tension cracks in the protective
bowl!
– Lamp replacement: Keep replacement intervals as specified by the lamp
manufacturer!
10
Explosion protected light fittings
Series: KXB S .... / KXB M .... / KXB L ....
7.
Prior to replacing or removing any components, observe the following:
Cut the apparatus off the voltage before opening it or carrying
out repairs!
Repairs that affect the explosion protection, may only be carried
out by Zumtobel or a qualified electrician in compliance with the
applicable national rules (IEC/EN 60079-19).
Only use certified genuine Zumtobel spare parts (see appropriate spare
parts list)!
8.
When the apparatus is disposed of, the respective national regulations on
waste disposal will have to be observed.
In case of disposal you can obtain additional information from your
Zumtobel branch.
Subject to modifications or supplement of the product range.

Repair

Disposal / Recycling
GB

Werbung

Inhaltsverzeichnis
loading

Verwandte Produkte für Zumtobel KXB S EVG ZONE2/22 BODY

Diese Anleitung auch für:

Kxb s evg zone2/22 tw bodyKxb m evg zone2/22 bodyKxb m evg zone2/22 tw bodyKxb l evg zone2/22 bodyKxb l evg zone2/22 tw body

Inhaltsverzeichnis