2.6 Operating Mode Description

Operating Mode
Description
ECO Mode
When the input voltage is within voltage regulated
range, UPS will power the output directly from the
mains. ECO is an abbreviation of Efficiency Corrective
Optimizer. In this mode, when the battery is fully
charged, the fan will stop working to save energy
Buck Mode when
When the input voltage is higher than the voltage
AC is normal
regulation range but lower than high loss point, the
buck AVR will be activated
Boost mode when
When the input voltage is lower than the voltage
AC is normal
regulation range but higher than low loss point, the
boost AVR will be deactivated
Battery Mode
When the input voltage is beyond the acceptable range
or power failure and alarm is sounding every 10 seconds,
UPS will backup power from battery
Standby Mode
UPS is powered off and no output supply power, but can
still charge batteries
Fault Mode
When a fault occurs, the ERROR icon and the fault code
will be displayed
2.7 Faults Reference Codes
Fault Event
Fault Code
Icon
Bus start fail
01
x
Bus over
02
x
Bus Under
03
x
Inverter soft start fail
11
x
Inverter voltage high
12
x
Inverter voltage low
13
x

2.8 Warning Indicator

Warning
Icon (Flashing
Low battery
Overload
Battery is not connected
Over Charge
Site wiring fault
Downloaded from
www.Manualslib.com
LCD Display
Fault Event
Fault Code
Inverter output short
14
Battery voltage too high
27
Battery voltage too low
28
Over temperature
41
Over load
43
Charger failure
13
Code
Alarm
Sounds every 2 seconds
Sounds every second
Sounds every 2 seconds
Sounds every 2 seconds
Sounds every 2 seconds
manuals search engine
Warning
EPO Enabled
Over temperature
Charger Failure
Battery fault
Battery replacement
EEPROM error
Note: "Site Wiring Fault" function can be enabled/disabled via software. Please check soft-
ware manual for the details.
Problems
No indication and alarm even though
the mains are normal
The icon
and the warning code
flashing on LCD display and alarm
is sounding every 2 seconds
The icon
,
code
flashing on LCD display and
alarm is sounding every 2 seconds
The icon
,
code
flashing on LCD display and
alarm is sounding every 2 seconds
Fault code is shown as 27 on LCD
Icon
display and alarm is continuously
x
sounding
Fault code is shown as 28 on LCD
x
display and alarm is continuously
x
sounding
x
The icon
,
code
flashing on LCD display and
alarm is sounding every second
x
Fault code is show as 43 and the icon
is lit on LCD display. Alarm sounds
continuously
Fault code is shown as 14 and alarm
sounds continuously
Fault code is shown as 01, 02, 03, 11,
12, 13 and 41 on LCD display and alarm
is continuously sounding
Battery backup time is shorter than
nominal value
Fault code is show as 45 on LCD display
and code is continuously sounding
Icon (Flashing
Code
Alarm
Sounds every 2 seconds
Sounds every 2 seconds
Sounds every 2 seconds
Sounds every 2 seconds
(UPS will turn off )
Sounds every 2 seconds
Sounds every 2 seconds
Cause
The AC input power is not
connected
The AC input is connected to the
UPS output
EPO function is activated
and the warning
Line and neutral conductors of UPS
input are reversed
and the warning
The external or internal battery is
incorrectly connected
Battery voltage is too high or the
charger is faulty
Battery voltage is too low or the
charger is faulty
and the warning
UPS is overloaded
The UPS automatically shut down
due to an overload at the output
The UPS automatically shut down
because of a short circuit on the UPS
A UPS internal fault has occurred
Batteries are not fully charged
Batteries are defective
The charger does not have output
and battery voltage is less than
10V/PC
Solution
Check if input power cord firmly connected to
the mains
Plug AC input power cord to AC input correctly
Set the circuit in closed position to disable EPO
function.
Rotate main power socket by 180° and then
connect to UPS system
Check if all batteries are connected
Contact your dealer
Contact your dealer
Remove excess loads from UPS output and
restart
Remove excess loads from the UPS output and
restart
Check output wiring and if connected devices
are in short circuit status
Contact your dealer
Charge the batteries for at least 5 hours and
then check capacity. If the problem persists,
consult your dealer
Contact your dealer to replace the batteries
Contact your dealer