Herunterladen Diese Seite drucken

Eaton P5-125/E Montageanweisung Seite 2

Werbung

P5-125(160)(250)(315)/EA/SVB,
P5-125(160)(250)(315)/EA/SVB-SW,
P5-160/EA/SVB-SW-SCM
0 I
1L1
1T1
1L2
1T2
1L3
1T3
P5-125(160)(250)(315)/EA/SVB-SW/HI10,
P5-125(160)(250)(315)/EA/SVB/HI10
0 I
1L1
1T1
1L2
1T2
1L3
1T3
7
8
HI10
PH1
A = 5
B = 6
UL60947-4-1, UL508
Temperature rating of wire 75°C
These devices are suitable for use on circuits capable of delivering
not more than 10kA rms symmetrical amperes 600V ac max. when
protected by Type RK1 fuses.
Use copper wire only.
Torque value for field wiring terminals:
HI....P5
2
0.5 - 2.5 mm
2
0.75 - 2.5 mm
Torque
0.8 Nm (7.0 lb-in)
2
2 /
Eaton Industries GmbH, Hein-Moeller-Straße 7-11, 53115 Bonn, Germany
© 2016 by Eaton Industries GmbH,
www.eaton.eu/documentation
(2 x)
o 13 mm - 17 mm
(o 0.51" - 0.67")
Typ
lb-in.
Nm
P5-125...
125
14
P5-160...
125
14
P5-250...
140
16
P5-315...
140
16
E
m
e
g r
P5-125(160)(250)(315)/EA/SVB/N,
P5-125(160)(250)(315)/EA/SVB-SW/N,
P5-160/EA/SVB-SW/N-SCM
0 I
1L1
1T1
1L2
1T2
1L3
1T3
2L1
2T1
P5-125/..., P5-160/...
P5-250/..., P5-315/...
o 6 mm
(o 0.24")
IEC60947-3 / EN60947-3 / VDE0660-107
Max Fuse Rating:
P5-125(160)/EA/SVB...
1 x 70 mm
2 x 25 mm
1 x 95 mm
2 x 35 mm
1 x 13 x 3
2 x 13 x 1.5
Torque
14 Nm (125 lb-in)
n e
y c
O
n
C
l a
S l
r e
c i v
: e
o L
l a c
e r
r p
s e
n e
a t
v i t
( e
All Rights Reserved
A
B
d
F 3 x
M5
PH2
Typ
Fuse characteristic
Numb Fuses
P5-125...
gG
P5-160...
gG
P5-250...
gG
P5-315...
gG
P5-250(315)/EA/SVB...
2
1 x 150 mm
2
2 x 50 mm
2
1 x 185 mm
2
2 x 70 mm
1 x 20 x 5
2 x 20 x 3
16 Nm (140 lb-in)
http://www.eaton.eu/aftersales) or +49 (0) 180 5 223822 (de, en)