GEIST
UPGRADEABLE PDU
TM
WITH FACILITY SIDE CABLE INSTALLATION
Quick Installation Guide
OVERVIEW
The Universal Power Distribution
Units (UPDU) are equipped with a
7- or 8-wire Panel Mount connector.
These units are intended to be
mated with a Facility Side Cable
(FSC) available for the unit. The FSC
connects to a single-phase AC
Mains circuit, a three-phase WYE or
Delta AC Mains circuit. The UPDUs
are provided with IEC C13- and/or
IEC C19-type outlets for connection
to external devices
.
Installation
1. Using appropriate hardware,
mount the unit to the rack.
2. Plug the FSC into the UPDU.
NOTE: It may be necessary to
install a cable support in order
to reduce strain on the Panel
Mount connector.
3. Plug the FSC into an appropriately
rated and protected branch
circuit.
4. Plug in the devices to be
powered by the UPDU.
NOTE: For devices powered by the
UPDU, sequential power up is
recommended to avoid a high
inrush current.
Configuring IP addressable
units
If the UPDU is equipped with an RJ45
Ethernet port for attachment to an
existing network, the UPDU is
configured with the following default
network settings to allow unit
configuration:
• IP address: 192.168.123.123
• Subnet Mask: 255.255.255.0
• Gateway: 192.168.123.1
The local PC network connection
must be configured as follows:
• IP Address: 192.168.123.x (where
x is 2-253, except 123)
• Subnet Mask: 255.255.255.0
Environmental
Temperature Limits
DESCRIPTION
Operating
Storage
* - DU00X2R1-18C137-0H02A9F00-S is 45°C (113°F) max (100% of max current rating) / 60°C (140°F)
max (50% of max current rating)
Humidity Limits
DESCRIPTION
Operating
Storage
Elevation Limits
DESCRIPTION
Operating
Storage
Electrical Ratings
INPUT RATING
CURRENT
VOLTAGE
(MAX)
24 A
200-240 VAC
200-240
40 A
VAC, 3W+PE
200-240/346-
24 A (UL)
415 VAC,
/ 32 A (CE)
3W+N+PE
100-240
48 A
VAC
100-240
24 A
VAC 3~
100-240/208-
16 A
415 VAC 3~
48 A (UL)
100-240
/ 63 A (CE)
VAC
100-240
48 A
VAC 3~
24 A (UL)
100-240/208-
/ 32 A (CE)
415 VAC 3~
MINIMUM
50°F (10°C)
-13°F (-25°C)
MINIMUM
5%
95% (non-condensing)
5%
95% (non-condensing)
MAXIMUM
10000 ft (3050 m)
50000 ft (15240 m)
FACTORY
SIDE
CABLE
FREQUENCY
Single-
50/60 Hz
Phase
4-wire
50/60 Hz
Delta
5-wire
50/60 Hz
WYE
Single-
50/60 Hz
Phase
4-wire
50/60 Hz
Delta
5-wire
50/60 Hz
WYE
Single-
50/60 Hz
Phase
4-wire
50/60 Hz
Delta
5-wire
50/60 Hz
WYE
MAXIMUM
140°F (60°C)*
149°F (65°C)
MAXIMUM
# OF
PANEL MOUNT
CIRCUIT
CONNECTOR
BRKRS
6
6
7-wire, 3 inch
6
3
3
3
6
8-wire, 1.5 inch
6
6
1
-