VERTIV
GEIST
TM
PDU AND UNIVERSAL PDU
Quick Installation Guide
Installing the rPDU
a.
Using appropriate hardware,
mount the unit to the rack.
b. Plug the PDU into an appropriately
rated and protected branch circuit
receptacle.
WARNING! PDUs supplied with
external ground stud have high
touch current. Earth connection is
essential prior to connecting
supply.
A #8 grounding stud, ring terminal
and nut have been provided on the
face of the device to facilitate
attachment to earth. Reference the
conductor size in the power cord
and PDU rating for appropriate
sizing of the external earth
conductor. Affix the provided ring
terminal to this wire, following
manufacturer's installation
instructions. Place the ring
terminal on the grounding stud
and torque the nut to the
appropriate torque listed in the
table below. Attach the other end
of the conductor to your facility's
earthing system.
STUD/
WIRE SIZE
NUT
SIZE
#8
<8AWG(10mm2)
#8
8AWG(10mm2)
M5
<8AWG(10mm2)
M5
8AWG(10mm2)
>8AWG(10mm2)
1/4"
20*
* NOTE: The wire retaining set screw in
the associated terminal must be torqued
to 16.5 in-lb (1.86 NM).
UPGRADEABLE
TM
Environmental
Universal Power
Distribution Unit
Upgradeable Basic,
Metered, Unit Monitored
Upgradeable Switched,
Outlet Monitored
* Note: DU00X2R1-18C137-0H02A9F00-S is 45°C (113°F) maximum (100% of maximum
current rating) / 60°C (140°F) maximum (50% of maximum current rating)
All PDUs
All PDUs
c. Plug in the devices that are to be
powered by the PDU.
d. Power-on the devices that are to
be powered by the PD.
TORQUE
NOTE:
- in.-lb.
recommended to avoid high
(Nm)
inrush current.
16.5 (1.86)
Installing the Universal PDU
27 (3.05)
The Universal Power Distribution Units
16.5(1.86)
(UPDU) are equipped with a 7 or 8-wire
27(3.05)
Panel Mount connector. These units are
intended to be mated with a Facility
27(3.05)
Side Cable available for the unit. The
Facility Side Cable connects to a single-
phase AC Mains circuit, a 3-phase WYE
or Delta AC Mains circuit. The Universal
PDUs are provided with IEC C13- and/or
IEC C19-type outlets for connection to
external devices.
TEMPERATURE
Operating
10°C to 60°C*
(50°F to 140°F)
10°C to 60°C
(50°F to 140°F)
10°C to 60°C
(50°F to 140°F) UL;
10°C to 50°C
(50°F to 122°F) CE
HUMIDITY
Operating
5% to 95%
(non-condensing)
ELEVATION
Operating
0 m to 3,050 m
(0 ft. to 10,000 ft.)
Sequential power-up is
Storage
-40°C to 70°C
(-40°F to 158°F)
-40°C to 70°C
(-40°F to 158°F)
-40°C to 70°C
(-40°F to 158°F)
Storage
5% to 95%
(non-condensing)
Storage
0 m to 12,200 m
(0 ft. to 40,000 ft.)
1. Using appropriate hardware, mount
the unit to the rack.
2. Plug the Facility Side Cable into the
Universal PDU.
NOTE: It may be necessary to
install a cable support in order to
reduce strain on the Panel Mount
connector.
3. Plug the Facility Side Cable into an
appropriately rated and protected
branch circuit.
4. Plug in the devices to be powered
by the Universal PDU.
NOTE: For devices powered by the
Geist UPDU, sequential power up is
recommended to avoid high inrush
current.
VM1246/SL-70646_REVA_09-20
1

Werbung

loading

Inhaltszusammenfassung für Vertiv GEIST GU2 Serie

  • Seite 1 VERTIV GEIST UPGRADEABLE PDU AND UNIVERSAL PDU Quick Installation Guide Installing the rPDU Environmental Using appropriate hardware, TEMPERATURE mount the unit to the rack. Operating Storage b. Plug the PDU into an appropriately Universal Power 10°C to 60°C* -40°C to 70°C Distribution Unit (-40°F to 158°F)
  • Seite 2 • IP Address: 192.168.123.x (where x 6. Place the cable into the strain- 2. Insert the Vertiv IMD Removal Tool is 2-253, except 123) relief slot in the IMD’s housing as as shown. Be sure to press the tool •...
  • Seite 3 VERTIV GEIST UPGRADEABLE PDU GU2 GEIST PDU IMD MODULES Quick Installation Guide Replacement Guide VM1246/SL-70646_REVA_09-20 VM1150/SL-70545_REV3_11-19...
  • Seite 4 To contact Vertiv Technical Support: visit www.Vertiv.com © 2020 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Group Corp.
  • Seite 5 VERTIV GEIST : AUFRÜSTBARE PDU UND UNIVERSELLE PDU Installations-Kurzanleitung Installation der rPDU Umgebungsbedingungen Montieren Sie das Gerät mit TEMPERATUR geeignetem Werkzeug am Rack. Betrieb Lagerung b. Schließen Sie die PDU an eine Universelle Power 10 °C bis 60 °C* -40 °C bis 70 °C...
  • Seite 6 5. Schließen Sie das Kabel an das es direkten Kontakt mit Ihrer Haut hat. PCs muss wie folgt konfiguriert werden: Ersatz-IMD-Modul an. 2. Setzen Sie das Vertiv • IP-Adresse: 192.168.123.x (wobei x 6. Platzieren Sie das Kabel in den IMD-Ausbauwerkzeug wie gezeigt ein.
  • Seite 7 VERTIV GEIST : AUFRÜSTBARE PDU GU2 GEIST PDU IMD MODULES Schnellinstallationsanleitung Replacement Guide VM1246/SL-70646_REVA_09-20 VM1150/SL-70545_REV3_11-19...
  • Seite 8 Der technische Kundendienst von Vertiv ist erreichbar unter: www.Vertiv.com © 2020 Vertiv Group Corp. Alle Rechte vorbehalten. Vertiv™ und das Vertiv-Logo sind Marken oder eingetragene Marken der Vertiv Group Corp. Alle anderen erwähnten Namen und Logos sind Handelsnamen, Marken oder eingetragene Marken der jeweiligen Eigentümer. Es wurden zwar alle Anstrengungen unternommen, um die Richtigkeit und Vollständigkeit dieses Dokuments zu gewährleisten, die Vertiv Group Corp.
  • Seite 9 PDU ACTUALIZABLE VERTIV GEIST Y PDU UNIVERSAL Guía de instalación rápida Instalación de la rPDU Requisitos ambientales Utilizando el hardware apropiado, TEMPERATURA monte la unidad en el rack. En funcionamiento En almacenamiento b. Conecte la PDU a un receptáculo Unidad universal de 10 °C a 60 °C*...
  • Seite 10 2. Inserte la herramienta de extracción • Dirección IP: 192.168.123.x (donde x 6. Coloque el cable en la ranura de del IMD Vertiv como se indica. es 2-253, excepto 123) alivio de tensión en la carcasa del Asegúrese de presionar la IMD como se indica.
  • Seite 11 PDU GU2 ACTUALIZABLE VERTIV GEIST GEIST PDU IMD MODULES Guía de instalación rápida Replacement Guide VM1246/SL-70646_REVA_09-20 VM1150/SL-70545_REV3_11-19...
  • Seite 12 Para ponerse en contacto con el servicio de asistencia técnica de Vertiv, visite www.Vertiv.com. © 2020 Vertiv Group Corp. Todos los derechos reservados. Vertiv™ y el logotipo de Vertiv son marcas comerciales o marcas comerciales registradas de Vertiv Group Corp.
  • Seite 13 PDU ÉVOLUTIVE ET PDU UNIVERSELLE VERTIV GEIST Guide d’installation rapide Installation de la PDU Spécifications environnementales a. Installez l’unité sur le rack à l’aide TEMPÉRATURE de la visserie appropriée. En fonctionnement Stockage b. Branchez la PDU dans la prise d’un Rampe d’alimentation...
  • Seite 14 6. Insérez le câble dans la fente anti- 2. Insérez l’outil de retrait du module • Adresse IP : 192.168.123.x (où x est traction du boîtier du module IMD, IMD Vertiv comme illustré. Alignez 2-253, sauf 123) comme illustré. l’outil sur la face avant du module •...
  • Seite 15 PDU GU2 ÉVOLUTIVE VERTIV GEIST GEIST PDU IMD MODULES Guide d’installation rapide Replacement Guide VM1246/SL-70646_REVA_09-20 VM1150/SL-70545_REV3_11-19...
  • Seite 16 Pour contacter l’équipe d’assistance technique de Vertiv, consultez le site www.Vertiv.com. © 2020 Vertiv Group Corp. Tous droits réservés. Vertiv™ et le logo Vertiv sont des marques de commerce ou des marques déposées de Vertiv Group Corp. Tous les autres noms et logos mentionnés sont des noms commerciaux, des marques de commerce ou des marques déposées de leurs détenteurs respectifs.
  • Seite 17 VERTIV GEIST UNITÀ PDU AGGIORNABILI E PDU UNIVERSALI Guida all'installazione rapida Installazione della rPDU Ambiente Utilizzare l'hardware appropriato TEMPERATURA per montare l'unità sul rack. Esercizio Stoccaggio b. Collegare l'unità PDU a una presa Unità di distribuzione Da 10°C a 60°C* Da -40°C a 70°C...
  • Seite 18 5. Collegare il cavo al modulo IMD in 2. Inserire lo strumento di rimozione IMD essere configurata come segue: sostituzione. Vertiv come mostrato. Assicurarsi di • Indirizzo IP: 192.168.123.x (dove x è 6. Posizionare il cavo nell'incavo anti- premere lo strumento in piano...
  • Seite 19 VERTIV GEIST UNITÀ PDU AGGIORNABILE GU2 GEIST PDU IMD MODULES Guida all'installazione rapida Replacement Guide VM1246/SL-70646_REVA_09-20 VM1150/SL-70545_REV3_11-19...
  • Seite 20 Per contattare l'assistenza tecnica Vertiv, visitare il sito www.Vertiv.com © 2020 Vertiv Group Corp. Tutti i diritti riservati. Vertiv™ e il logo Vertiv sono marchi o marchi registrati di Vertiv Group Corp. Tutti gli altri nomi e loghi citati sono nomi commerciali, marchi o marchi registrati dei rispettivi proprietari.
  • Seite 21 PDU ATUALIZÁVEL E PDU UNIVERSAL VERTIV GEIST Guia de instalação rápida Instalação do rPDU Ambiental Instale a unidade no rack usando TEMPERATURA as ferramentas adequadas. Durante a operação Armazenamento b. Ligue o PDU a um receptáculo de Unidade de Distribuição de 10 °C a 60 °C*...
  • Seite 22 PDU ATUALIZÁVEL GU2 VERTIV GEIST Guia de instalação rápida Tensões elétricas do UPDU Geist TENSÃO DE ENTRADA CONECTOR DE LOCAL Nº DE DISJUNTO- SUPORTE DO CABO RES DE SAÍDA CORRENTE PAINEL TENSÃO FREQUÊNCIA (MÁX) 24 A 240 VAC 50/60 Hz Fase única...
  • Seite 23 PDU ATUALIZÁVEL GU2 VERTIV GEIST GEIST PDU IMD MODULES Guia de instalação rápida Replacement Guide VM1246/SL-70646_REVA_09-20 VM1150/SL-70545_REV3_11-19...
  • Seite 24 Para entrar em contato com o suporte técnico da Vertiv, visite www.Vertiv.com © 2020 Vertiv Group Corp. Todos os direitos reservados. Vertiv™ e o logotipo da Vertiv são marcas comerciais ou marcas comerciais registradas da Vertiv Group Corp. Todos os demais nomes e logotipos mencionados aqui são nomes comerciais, trademarks ou marcas comerciais registradas de seus respectivos proprietários.
  • Seite 25 アップグレード可能 VERTIV GEIST PDU および ユニバーサル PDU クイック ・ インストレーション ・ ガイド rPDU の設置 環境 適切な金具を使用して、 ユニッ トをラッ 温度 クに取り付けます。 作動時 保管時 b. 適切な定格の保護された分岐回路 ユニバーサル配電ユニッ ト 10°C ~ 60°C* -40°C ~ 70°C レセプタクルに PDU を接続します。 アップグレード可能、 ベーシッ 10°C ~ 60°C -40°C ~...
  • Seite 26 うに構成する必要があります。 5. 交換する IMD モジュールにケーブ ます。 • IP アドレス : 192.168.123.x ( x が 2-253 ルを接続します。 2. 図に示すように、 Vertiv IMD 取り外 の場合、 123 を除く) 6. 図に示すように、 IMD のハウジング しツールを挿入します。 ツールを傾 • サブネッ トマスク : 255.255.255.0 のストレイン ・ リリーフ ・ スロッ トの中...
  • Seite 27 アップグレード可能 PDU GU2 VERTIV GEIST GEIST PDU IMD MODULES クイック ・ インストレーション ・ ガイド Replacement Guide VM1246/SL-70646_REVA_09-20 VM1150/SL-70545_REV3_11-19...
  • Seite 28 Vertiv テクニカル ・ サポートへのお問い合わせについては、 www.Vertiv.com を参照してく ださい © 2020 Vertiv Group Corp. 全著作権所有。 Vertiv™ および Vertiv ロゴは、 Vertiv Group Corp. の商標または登録商標です。 言及されている他のすべての名称およびロゴは、 それぞれの所有者の商号、 商標、 または登録商標です。 本文書の正確性および完全性については万全を期しておりますが、 Vertiv Group Corp. は、 記載情報の使用に起因する 損害または誤記や脱落に対しては一切の責任を負わず、 かつそのすべての賠償責任を拒否します。 仕様は予告なく変更される可能性があります。 VM1246/SL-70646_REVA_09-20...
  • Seite 29 VERTIV GEIST 可升级 PDU 和通用 PDU 快速安装指南 安装 rPDU 环境规格 使用合适的五金件将设备安装至机 温度 架。 工作 存储 b. 将 PDU 插入具有相应额定值且经 10°C 至 60°C* -40°C 至 70°C 通用配电设备 过适当保护的分支电路。 10°C 至 60°C -40°C 至 70°C 可升级基础型,带计量,设 警告!带有外部接地桩的 PDU 具 备受监控 有较高的接触电流。连接电源之 10°C 至 60°C UL;...
  • Seite 30 本地 PC 网络连接必须配置为: 5. 将电缆连接到 IMD 更换模块上。 露的皮肤接触。 • IP 地址:192.168.123.x(其中, 6. 如图所示,将电缆放入 IMD 外壳 2. 如图所示插入 Vertiv IMD 移除工 x 为 2-253,但 123 除外) 中的应力释放槽。 具 。 请 务 必 水 平 插 入 该 工 具 并 按 • 子网掩码:255.255.255.0 压,直到工具与...
  • Seite 31 VERTIV GEIST 可升级 PDU GU2 GEIST PDU IMD MODULES Replacement Guide 快速安装指南 VM1246/SL-70646_REVA_09-20 VM1150/SL-70545_REV3_11-19...
  • Seite 32 如需联系 Vertiv 技术支持,请访问:www.Vertiv.com © 2020 Vertiv Group Corp. 保留所有权利。Vertiv™ 和 Vertiv 徽标是 Vertiv Group Corp. 的商标或注册商标。本文提及的所有其他名称和徽标均为其各自所有者的产品名称、 商标或注册商标。尽管我们已采取适当措施确保本文件的准确性和完整性,但对于因使用这些信息或任何错误或遗漏而造成的损害,Vertiv Group Corp. 概不承担任何责任和义务。 规格的更改将不另行通知。 VM1246/SL-70646_REVA_09-20...
  • Seite 33 VERTIV GEIST 업그레이드 가능 PDU 및 UNIVERSAL PDU 빠른 설치 설명서 rPDU 설치 작동 환경 온도 적절한 하드웨어를 사용하여 장치를 랙에 탑재합니다. 작동 보관 Universal 전원 분배 장치 10°C~60°C* -40°C~70°C b. PDU를 적합한 정격 및 보호 지선회로 콘센트에 연결합니다. 경고! 외부 접지 스터드가 함께...
  • Seite 34 6. 그림과 같이 IMD 하우징의 변형 팔 위에 착용하십시오. • IP 주소: 192.168.123.x(여기에서 123 을 제외하고 x는 2-253) 방지 슬롯에 케이블을 넣습니다. Vertiv IMD 보이는 것처럼 제거 • 서브넷 마스크: 255.255.255.0 7. PDU에 남는 케이블을 다시 넣고 도구를 삽입하십시오. 도구가...
  • Seite 35 VERTIV GEIST 업그레이드 가능 PDU GU2 GEIST PDU IMD MODULES Replacement Guide 빠른 설치 설명서 VM1246/SL-70646_REVA_09-20 VM1150/SL-70545_REV3_11-19...
  • Seite 36 Vertiv 기술 지원부에 문의하려면 www.Vertiv.com 을 방문하십시오. © 2020 Vertiv Group Corp. All rights reserved. Vertiv™ 및 Vertiv 로고는 Vertiv Group Corp.의 상표 및 등록 상표입니다. 기타 언급되는 모든 이름 및 로고는 해당 소유주의 상호, 상표 또는 등록 상표입니다. 본 문서에서는 정확성 및 완전성을 보장하기 위해 모든 예방 조치를 취했지만 Vertiv Group Corp.는 본 정보의 사용으로 비롯된 손상이나 모든 오류...
  • Seite 37 VERTIV GEIST 升級型 PDU 與 UPDU 快速安裝指南 安裝 rPDU 環境規格 溫度 使用適當的硬體,將設備安裝到機 架上。 工作 儲存 b. 將 PDU 插入具有適當額定值並受到 通用配電設備 (UPDU) 10°C 至 60°C* -40°C 至 70°C 恰當保護的分支電路。 10°C 至 60°C -40°C 至 70°C 升級型基本,可計量,設備 警告!配備外部接地樁的配電設備 監控 (PDU) 具有高接觸電流。在連接電 10°C 至 60°C UL;...
  • Seite 38 提示:請確保戴上腕帶再繼續操  子網路遮罩:255.255.255.0 閘 下背膠,貼到 PDU 上。將腕帶戴到 作。參見步驟 1 瞭解詳細資訊。 道:192.168.123.1 手臂上,使其直接接觸皮膚。 5. 將線纜連接到用於更換的 IMD 模組。 2. 如圖所示,插入 Vertiv IMD 拆卸工 本機 PC 網路連接必須設定如下: 6. 如圖所示,將線纜放入 IMD 外殼中 具。請務必水平插入該工具,按入 • IP 位址:192.168.123.x(其中 x 為 的應力釋放槽。 直到工具與 IMD 表面齊平。對於一 2-253 之間的任意數字,123 除...
  • Seite 39 VERTIV GEIST 升級型 PDU GU2 GEIST PDU IMD MODULES Replacement Guide 快速安裝指南 VM1246/SL-70646_REVA_09-20 VM1150/SL-70545_REV3_11-19...
  • Seite 40 如需聯絡 Vertiv 技術支援:請造訪 www.Vertiv.com © 2020 Vertiv Group Corp. 保留所有權利。Vertiv™ 和 Vertiv 標誌是 Vertiv Group Corp. 的商標或註冊商標。所有提及的其他名稱和標誌屬其各自所有人的商品名、商標或註冊商 標。雖然已採取所有預防措施來確保本文的準確性與完整性,但對於因使用本資訊或本資訊中的任何錯誤或疏漏造成的損害,Vertiv Group Corp. 概不負責。規格可能會變更,恕不另 行通知。 VM1246/SL-70646_REVA_09-20...
  • Seite 41 VERTIV GEIST ‫ אוניברסלי הניתן לשדרוג‬PDU-‫ ו‬PDU ‫מדריך להתקנה מהירה‬ rPDU ‫התקנת‬ ‫סביבה‬ ‫א.  בעזרת הציוד המתאים, חבר את‬ ‫טמפרטורה‬ .‫היחידה למתלה‬ ‫באחסון‬ ‫בהפעלה‬ 70°C ‫°04- עד‬C 60°C * ‫°01 עד‬C ‫יחידת חלוקת כוח‬ ‫ לשקע מעגל חשמלי‬PDU-‫ב.  חבר את ה‬...
  • Seite 42 ‫הכנס את הכבל לחריץ כדי להקל על‬ .‫במגע עם עור חשוף‬ ‫יש להגדיר את חיבור רשת המחשב המקומי‬ .‫ כפי שמוצג‬IMD ‫המתח בבית‬ ‫ כפי‬Vertiv IMD ‫הכנס את כלי הסרת‬ :‫באופן הבא‬ ‫תחוב את הכבל העודף בחזרה‬ ‫שמוצג. הקפד ללחוץ על הכלי בגובה‬...
  • Seite 43 ‫ עם אופציה לשדרוג‬VERTIV GEIST PDU GU2 GEIST PDU IMD MODULES ‫מדריך להתקנה מהירה‬ Replacement Guide VM1246/SL-70646_REVA_09-20 VM1150/SL-70545_REV3_11-19...
  • Seite 44 ‏ ‏‬Vetriv‫כדי‏לפנות‏לתמיכה‏טכנית‏של‏‬ ‫. כל השמות והסמלים המוזכרים האחרים הם שמות‬Vertiv Group Corp. ‫ הם סימנים מסחריים או סימנים מסחריים רשומים של‬Vertiv ‫™ והסמל של‬Vertiv .‫ 0202 © . כל הזכויות שמורות‬Vertiv Group Corp. ‫ אינה מביעה כל אחריות ואינה‬Vertiv Group Corp. ,‫מסחריים, סימנים מסחריים או סימנים מסחריים רשומים של בעליהם בהתאמה. בעוד שיש לנקוט בכל אמצעי זהירות כדי להבטיח דיוק ושלמות במסמך זה‬...
  • Seite 45 УСТРОЙСТВО РАСПРЕДЕЛЕНИЯ ПИТАНИЯ VERTIV GEIST С ВОЗМОЖНОСТЬЮ ОБНОВЛЕНИЯ И УНИВЕРСАЛЬНОЕ УСТРОЙСТВО РАСПРЕДЕЛЕНИЯ ПИТАНИЯ Краткое руководство по установке Монтаж устройства Условия окружающей среды распределения питания rPDU ТЕМПЕРАТУРА А. С помощью подходящих Эксплуатация Хранение инструментов выполните монтаж устройства в стойке. Универсальное устройство...
  • Seite 46 УСТРОЙСТВО РАСПРЕДЕЛЕНИЯ ПИТАНИЯ VERTIV GEIST С ВОЗМОЖНОСТЬЮ ОБНОВЛЕНИЯ Краткое руководство по установке Расчетные электрические параметры универсальных устройств распределения питания Geist РАСЧЕТНЫЕ ПАРАМЕТРЫ ВХОДОВ КОЛ-ВО АВТО- ЛОКАЛИЗОВАННЫЙ МАТИЧЕСКИХ БЛОЧНЫЙ РАЗЪЕМ КАБЕЛЬ ВЫКЛЮЧАТЕЛЕЙ ТОК (МАКС.) НАПРЯЖЕНИЕ ЧАСТОТА 200… 240 В перем. 24 A 50/60 Гц...
  • Seite 47 GEIST PDU IMD MODULES УСТРОЙСТВО РАСПРЕДЕЛЕНИЯ ПИТАНИЯ VERTIV GEIST Replacement Guide С ВОЗМОЖНОСТЬЮ ОБНОВЛЕНИЯ Краткое руководство по установке VM1246/SL-70646_REVA_09-20 VM1150/SL-70545_REV3_11-19...
  • Seite 48 Информацию о доступе к центру технической поддержки компании Vertiv см. на веб-сайте www.Vertiv.com. © Vertiv Group Corp., 2020. Все права защищены. Vertiv™ и логотип Vertiv являются товарными знаками или зарегистрированными товарными знаками корпорации Vertiv Group Corp. Все остальные названия и логотипы, используемые в настоящем документе, являются товарными знаками или зарегистрированными товарными знаками соответствующих...
  • Seite 49 PDU ACTUALIZABLE VERTIV GEIST Y PDU UNIVERSAL Guía de instalación rápida Instalación de la rPDU Condiciones ambientales a. Usando el hardware apropiado, TEMPERATURA monte la unidad en el rack. En funcionamiento Almacenamiento b. Enchufe la PDU en un receptáculo Unidad de distribución de De 10 °C a 60 °C*...
  • Seite 50: Instalación

    2. Inserte la herramienta de extracción es 2-253, excepto 123) 6. Coloque el cable en la ranura de de Vertiv IMD como se muestra. • Máscara de subred: 255.255.255.0 alivio de tensión en la carcasa del Asegúrese de presionar la IMD como se muestra.
  • Seite 51 PDU ACTUALIZABLE VERTIV GEIST GEIST PDU IMD MODULES Guía de instalación rápida Replacement Guide VM1246/SL-70646_REVA_09-20 VM1150/SL-70545_REV3_11-19...
  • Seite 52 Para ponerse en contacto con el servicio de asistencia técnica de Vertiv, visite www.Vertiv.com © 2020 Vertiv Group Corp. Todos los derechos reservados. Vertiv™ y el logotipo de Vertiv son marcas comerciales o marcas comerciales registradas de Vertiv Corp. Todos los demás nombres y logotipos a los que se hace referencia son nombres comerciales, marcas comerciales o marcas comerciales registradas de sus respectivos propietarios.
  • Seite 53 )PDU( ‫) ووحدة توزيع الطاقة‬PDU( ‫وحدة توزيع الطاقة‬ VERTIV GEIST ‫العالمية من‬ ‫قابلة للتجديد‬ ‫دليل التركيب السريع‬ rPDU ‫تركيب‬ ‫العوامل البيئية‬  .‫أ‬ ‫درجة الحرارة‬ ‫باستخدام األجهزة المناسبة، قم بتركيب الوحدة على‬ .‫الحامل‬ ‫السعة التخزينية‬ ‫التشغيل‬ ‫04- درجة مئوية إلى 07 درجة مئوية‬...
  • Seite 54 • ‫ضع الكبل داخل فتحة تخفيف الضغط‬ ،253 ‫ إلى القيمة من 2 إلى‬x ‫يرمز‬ ‫ كما‬Vertiv ‫ من‬IMD ‫أد خ ِل أداة إزالة وحدة‬ ‫ كما هو‬IMD ‫الموجودة في مبيت وحدة‬ )123 ‫باستثناء الرقم‬ ‫هو موضح. وتأكد من الضغط على األداة في‬...
  • Seite 55 VERTIV GEIST ‫ القابلة للتحديث من‬PDU GU2 ‫وحدة‬ GEIST PDU IMD MODULES ‫دليل التركيب السريع‬ Replacement Guide VM1246/SL-70646_REVA_09-20 VM1150/SL-70545_REV3_11-19...
  • Seite 56 ‫ أي مسؤولية و ت ُ خلي مسؤوليتها التامة عن األضرار التي تنتج عن‬Vertiv Group Corp. ‫عالمات تجارية أو عالمات تجارية مسجلة للشركات المالكة لها. لقد تم اتخاذ جميع االحتياطات التي تضمن دقة هذه الوثيقة واكتمالها، ومع ذلك ال تتحمل شركة‬...