Herunterladen Diese Seite drucken
Eaton IZM-Serie Bedienungsanleitung

Eaton IZM-Serie Bedienungsanleitung

Kodiervorrichtung

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

05/10 AWA1230-2435
IZM cassette IZM32, IZME40, IZM40,
IZM97, IZM63, and IZM99 frame
rejection bracket replacement kit
(1) Only qualified electrical persOnnel shOuld
be permitted tO wOrk On the equipment.
(2) always de-energize primary and
secOndary circuits if a circuit breaker
cannOt be remOved tO a safe wOrk lOcatiOn.
(3) drawOut circuit breakers shOuld be
levered (racked) Out tO the discOnnect
pOsitiOn.
(4) all circuit breakers shOuld be switched
tO the Off pOsitiOn and mechanism springs
discharged.
failure tO fOllOw these steps fOr all
prOcedures described in this instructiOn
leaflet cOuld result in death, bOdily injury,
Or prOperty damage.
the instructiOns cOntained in this awa and On
prOduct labels have tO be fOllOwed. Observe
the five safety rules:
– discOnnecting
– ensure that devices cannOt be
accidentally restarted
– verify isOlatiOn frOm the supply
– earthing and shOrt-circuiting
– cOvering Or prOviding barriers tO
adjacent live parts
discOnnect the equipment frOm the supply.
use Only authOrized spare parts in the repair
Of the equipment. the specified maintenance
intervals as well as the instructiOns fOr
repair and exchange must be strictly adhered
tO prevent injury tO persOnnel and damage tO
the switchbOard.
Effective May 2010
 warning
 warning
2A10995H01
Section 1: General information
IZM drawout circuit breakers come in a variety
of continuous current and interrupting ratings. To
prevent the insertion of a drawout circuit breaker
into a cassette with which it is incompatible,
rejection interlock key plates are provided for
both the circuit breaker and the cassette. As the
breaker is pushed into the cassette, the interlock
pins on the breaker move past the pins in the
cassette if they are compatible.
Required tools
10 mm socket and drive
10 mm wrench
Kit parts identification
Refer to Figure 1 for visual identification of the
parts listed below:
(A) Rejection bracket (one)
(B) M6 stop nut (six)
(C) M6 x 12 mm hex bolt (six)
(D) M6 serrated lock washer (six)
(E) M6 x 10 mm crimptite screw (two)
(B)
(C)
(D)
(A)
Figure 1. Contents of Kit
(E)

Werbung

loading

Inhaltszusammenfassung für Eaton IZM-Serie

  • Seite 1 05/10 AWA1230-2435 Effective May 2010 2A10995H01 IZM cassette IZM32, IZME40, IZM40, IZM97, IZM63, and IZM99 frame rejection bracket replacement kit Section 1: General information  warning IZM drawout circuit breakers come in a variety (1) Only qualified electrical persOnnel shOuld of continuous current and interrupting ratings.
  • Seite 2 IZM63N, IZM99N IZM40H, IZM63H, IZM99H IZM63N, IZM99N for 5000–6300A IZM63H, IZM99H for 5000–6300A Figure 3. Step 2 Eaton Industries GmbH Electrical Sector ©2010 by Eaton Industries GmbH Änderungen vorbehalten Subject to alterations 05/10 AWA1230-2435 / Z8803 Moon/Doku/Heng Printed in USA (05/10)
  • Seite 3 05/10 AWA1230-2435 Gültig ab Mai 2010 2A10995H01 Kodiervorrichtung für Ausfahrtechnik des IZM32/IZM97, IZM40, IZM63/IZM99 Abschnitt 1: Allgemeine  warnUng Informationen (1) Die instanDhaltUng Darf nUr DUrch entsprechenD elektrontechnisch IZM Leistungsschalter in Ausfahrtechnik qUalifiziertes personal erfolgen. gibt es in verschiedenen Nennströmen und (2) Vor Beginn Der arBeiten mUss Der Bemessungskurzschlussausschaltvermögen.
  • Seite 4 IZM63N, IZM99N IZM40H, IZM63H, IZM99H IZM63N, IZM99N für 5000–6300A IZM63H, IZM99H für 5000–6300A Abbildung 3. Schritt 2 Eaton Industries GmbH Electrical Sector ©2010 by Eaton Industries GmbH Änderungen vorbehalten Subject to alterations 05/10 AWA1230-2435 / Z8803 Moon/Doku/Heng Printed in USA (05/10)

Diese Anleitung auch für:

Izm32Izme40Izm40Izm97Izm63Izm99