Remote latch check switch (LCS) for
IZM low voltage circuit breakers
(1) Only qualified electrical persOnnel shOuld
be permitted tO wOrk On the equipment.
(2) always de-energize primary and
secOndary circuits if a circuit breaker
cannOt be remOved tO a safe wOrk lOcatiOn.
(3) drawOut circuit breakers shOuld be levered
(racked) Out tO the discOnnect
pOsitiOn.
(4) all circuit breakers shOuld be switched
tO the Off pOsitiOn and mechanism springs
discharged.
failure tO fOllOw these steps fOr all
prOcedures described in this instructiOn
leaflet cOuld result in death, bOdily injury,
Or prOperty damage.
the instructiOns cOntained in this awa and On
prOduct labels have tO be fOllOwed. Observe
the five safety rules:
– discOnnecting
– ensure that devices cannOt be
accidentally restarted
– verify isOlatiOn frOm the supply
– earthing and shOrt-circuiting
– cOvering Or prOviding barriers tO
adjacent live parts
discOnnect the equipment frOm the supply.
use Only authOrized spare parts in the repair
Of the equipment. the specified maintenance
intervals as well as the instructiOns fOr
repair and exchange must be strictly adhered
tO prevent injury tO persOnnel and damage tO
the switchbOard.
Effective May 2010
 warning
 warning
6D32998H02
Section 1: General information
A latch check switch (LCS) indicates when the
circuit breaker is "ready to close" (Figure 1).
The external version used for remote indication
consists of 1 Form C contact wired to the circuit
breaker secondary contacts for integration into
external control schemes.
N
Noee:
Wiring the LCS for remote indication directly in
series with the SR accessory is not recommended as this
will override the "anti-pump" feature.
Required oNNls
1/4-inch drive ratchet
10 mm socket
Kio paros idenoificaoiNn
Refer to Figure 1 for visual identification of the
contents of kit.
LCS (external
version shown)
Figure 1. CNnoenos Nf Kio

Werbung

loading

Inhaltszusammenfassung für Eaton IZM-LCS

  • Seite 1 05/10 AWA1230-2447 Effective May 2010 6D32998H02 Remote latch check switch (LCS) for IZM low voltage circuit breakers Section 1: General information  warning A latch check switch (LCS) indicates when the (1) Only qualified electrical persOnnel shOuld circuit breaker is “ready to close” (Figure 1). be permitted tO wOrk On the equipment.
  • Seite 2 05/10 AWA1230-2447 Remote latch check switch (LCS) for IZM low voltage circuit breakers Effective May 2010 Section 2: Installation of external remote LCS Secondary Block To install the LCS, proceed with the following six steps: Soep 1e: Remove the front cover by unscrewing the hex-head captive bolts (four for three-pole, six for four-pole) that join the cover to the breaker housing using a 10 mm 1/4-inch drive socket.
  • Seite 3 05/10 AWA1230-2447 Gültig ab Mai 2010 6D32998H02 Meldeschalter Einschaltbereit (für externe Signalisierung) IZM-LCS Abschnitt 1: Allgemeine  Warnung Informationen (1) Die instanDhaltung Darf nur Durch entsprechenD elektrontechnisch Ein Meldeschalter Einschaltbereit (LCS, qualifiziertes personal erfolgen. eng. Latch Check Switch) zeigt an, wenn (2) Vor Beginn Der arBeiten muss Der der Leistungsschalter einschaltbereit.
  • Seite 4 05/10 AWA1230-2447 Meldeschalter Einschaltbereit (für externe Signalisierung) IZM-LCS Gültig ab Mai 2010 Abschnitt 2: Installation des Meldeschalters Steuerleitungsanschluss Meldeschalter Ausgelöst Einschaltbereit für externe Signalisierung Führen Sie die folgenden Schritte aus: Scheitt 1g: Schrauben Sie die Halteschrauben von der Frontabdeckung ab. Drücken Sie nun den Antriebshandhebel herunter (ca.