05/10 AWA1230-2447
Remote latch check switch (LCS) for
IZM low voltage circuit breakers
(1) Only qualified electrical persOnnel shOuld
be permitted tO wOrk On the equipment.
(2) always de-energize primary and
secOndary circuits if a circuit breaker
cannOt be remOved tO a safe wOrk lOcatiOn.
(3) drawOut circuit breakers shOuld be levered
(racked) Out tO the discOnnect
pOsitiOn.
(4) all circuit breakers shOuld be switched
tO the Off pOsitiOn and mechanism springs
discharged.
failure tO fOllOw these steps fOr all
prOcedures described in this instructiOn
leaflet cOuld result in death, bOdily injury,
Or prOperty damage.
the instructiOns cOntained in this awa and On
prOduct labels have tO be fOllOwed. Observe
the five safety rules:
– discOnnecting
– ensure that devices cannOt be
accidentally restarted
– verify isOlatiOn frOm the supply
– earthing and shOrt-circuiting
– cOvering Or prOviding barriers tO
adjacent live parts
discOnnect the equipment frOm the supply.
use Only authOrized spare parts in the repair
Of the equipment. the specified maintenance
intervals as well as the instructiOns fOr
repair and exchange must be strictly adhered
tO prevent injury tO persOnnel and damage tO
the switchbOard.
Effective May 2010
warning
warning
6D32998H02
Section 1: General information
A latch check switch (LCS) indicates when the
circuit breaker is "ready to close" (Figure 1).
The external version used for remote indication
consists of 1 Form C contact wired to the circuit
breaker secondary contacts for integration into
external control schemes.
N
Noee:
Wiring the LCS for remote indication directly in
series with the SR accessory is not recommended as this
will override the "anti-pump" feature.
Required oNNls
1/4-inch drive ratchet
•
10 mm socket
•
Kio paros idenoificaoiNn
Refer to Figure 1 for visual identification of the
contents of kit.
LCS (external
version shown)
Figure 1. CNnoenos Nf Kio