Technical Data

Terminal designation:
Wire connection
Screw terminals
(integrated):
Insulation of wires
or sleeve length:
Plug in with screw terminals
max. cross section
for connection:
Insulation of wires
or sleeve length:
Plug in with cage
clamp terminals
max. cross section
for connection:
min. cross section
for connection:
Insulation of wires
or sleeve length:
Wire fixing:
Mounting:
Weight:
Dimensions
Width x height x depth
LG 5933:
LG 5933 PC:
LG 5933 PS:
EN 50 005
DIN 46 228-1/-2/-3/-4
1 x 4 mm
solid or
2
1 x 2.5 mm
stranded ferruled (isolated)
2
or
2 x 1.5 mm
stranded ferruled (isolated)
2
or 2 x 2.5 mm
solid
2
8 mm
1 x 2.5 mm
solid or
2
1 x 2.5 mm
2
stranded ferruled (isolated)
8 mm
1 x 4 mm
solid or
2
1 x 2.5 mm
stranded ferruled (isolated)
2
0.5 mm
2
12
mm
±0.5
Plus-minus terminal screws M 3.5
box terminals with wire protection or
cage clamp terminals
DIN rail
IEC/EN 60 715
220 g
22.5 x 90 x 121 mm
22.5 x 111 x 121 mm
22.5 x 104 x 121 mm

Standard Type

LG 5933.48 DC 24 V
Article number:
• Output:
• Nominal voltage U
:
N
• Width:

Ordering Example

LG 5933 .48
PS
DC 24 V

Troubleshooting

Failure
LED "Power" does not light up
LED "K1" lights up,
but "K2" remains off
or
LED "K2" lights up,
but "K1" remains off
Device cannot be activated

Maintenance and repairs

- The device contains no parts that require maintenance.
- In case of failure, do not open the device but send it to manufacturer
for repair.
15
0058247
3 NO contacts, 1 NC contact
DC 24 V
22.5 mm
Nominal voltage
Type of terminals
without indication:
terminal blocks fixed
with screw terminals
PC (plug in cage clamp):
pluggable terminal blocks
with cage clamp terminals
PS (plug in screw):
pluggable terminal blocks
with screw terminals
Contacts
Type
Potential cause
Power supply not connected
- Safety relay K1 e.g. K2 is welded
(replace device)
- The 2-Hand-buttons have not been
operated simultaneously within ≤ 0,5s
- Safety relay is welded
(replace device)
- Feddback circuit Y1-Y2
not closed
- The 2-Hand-buttons have not been
operated simultaneously within ≤ 0,5s
LG 5933 / 27.06.16 en / 718

Werbung