Herunterladen Inhalt Inhalt Diese Seite drucken

Options; Assembly; Start-Up; Setting Outlet Pressure - resideo Braukmann D06F Einbauanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 8
2.5 D06FI
Media
Medium:
Connections/Sizes
Connection sizes:
Nominal sizes:
Pressure values
Max. inlet pressure with clear
filter bowl:
Max. inlet pressure with
stainless steel filter bowl:
Outlet pressure:
Preset outlet pressure:
Min. pressure drop:
Operating temperatures
Max. operating temperature
medium (10 bar/stainless
steel filter bowl):
Max. operating temperature
medium accord. to EN 1567:
Note:
Use the SM06T brass filter bowl, if the valve can be
exposed to UV radiation or solvent vapors.
3

Options

For Options visit homecomfort.resideo.com/europe
4

Assembly

4.1 Installation Guidelines
Horizontal and vertical installation position possible
Install shut-off valves
The installation location should be protected against
frost and be easily accessible
– Pressure gauge can be read off easily
– Simplified maintenance and cleaning
To guarantee perfect functioning, a filter must be
inserted ahead of the pressure reducing valve
Provide a straight section of pipework of at least five
times the nominal valve size after the pressure
reducing valve (in accordance with EN 806-2)
Requires regular maintenance in accordance with
EN 806-5
4.2 Assembly instructions
1.
Rinse pipeline well
2.
Install pressure reducing valve
• Observe flow direction
• Install without tension or bending stresses
3.
Screw in the sealing plugs manually
Drinking water
1
/
" - 2"
2
DN15 - DN50
16 bar
25 bar
1.5 - 6 bar
3 bar
1 bar
70 °C
30 °C
GB
5

Start-up

5.1 Setting outlet pressure

Set outlet pressure min. 1 bar under inlet pressure.
1.
Close shut-off valve on inlet
2.
Release pressure on outlet side (e.g. through water
tap)
3.
Install pressure gauge
4.
Close shut-off valve on outlet
5.
D06F, D06F-LF, D06FN, D06FI:
Loosen slotted screw
• Do not remove slotted screw
D06FH:
Loosen slotted screw and unscrew completely,
remove handle
6.
Slacken tension in compression spring
• Turn adjustment handle counter clockwise (-) until
it does not move any more
7.
Slowly open shut-off valve on inlet
8.
Turn the adjuster knob until the setting scale displays
the desired value
9.
D06F, D06F-LF, D06FN, D06FI:
Retighten slotted screw
D06FH:
Replace the handle
Retighten slotted screw
10.
Slowly open shut-off valve on outlet
6

Maintenance

In order to comply with EN 806-5, water fixtures must
be inspected and serviced on an annual basis.
As all maintenance work must be carried out by an
installation company, it is recommended that a
servicing contract should be taken out.
In accordance with EN 806-5, the following measures must
be taken:
6.1 Inspection
1.
Close shut-off valve on outlet
2.
Check outlet pressure using a pressure meter when
there is zero through-flow
• If the pressure is increasing slowly, the valve may
be dirty or defective. In this instance, carry out
servicing and cleaning (See 6.2 Maintenance)
3.
Slowly open shut-off valve on outlet
6
MU1H-1002GE23 R0120

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis

Fehlerbehebung

loading

Inhaltsverzeichnis