1. Safety Guidelines
1. Follow the installation instructions.
2. Use the appliance
• according to its intended use
• in good condition
• with due regard to safety and risk of danger.
3. Note that the appliance is exclusively for use in the appli-
cations detailed in these installation instructions. Any
other use will not be considered to comply with require-
ments and would invalidate the warranty.
4. Please take note that any assembly, commissioning,
servicingandadjustmentworkmayonlybecarriedout by
authorized persons.
5. Immediatelyrectifyanymalfunctionswhichmayinfluence
safety.
2. Description of function
Spring loaded check valves have amoving seal disc whichis
lifted off the seat by a greater or lesser amount depending on
the flow rate through the valve. If the flow falls towards zero,
then the spring pushes the disc back onto the seat and seals
the waterway.
To ensure continuing correct function it is recommended that
check valves be regularlychecked and maintained (as speci-
fied in EN1717).
3. Application
Medium
Drinking water
Inlet pressure
max. 16.0 bar
4. Technical data
Operating temperature 65 °C
Opening pressure
approx. 0.05 bar
Connection size
DN40 - DN300
5. Scope of delivery
The check valve comprises:
• Housing with flanges
• Housing end casing with flanges
• Test and drain plugs
• Disc and discguide
• Spring
• Disc lip seal ring
6. Options
RV283P-... A = With drilled flanges, PN16, ISO 7005-2,
EN 1092-1, DN40 - DN300,
EPDM lip seal ring
Connection size
7. Assembly
7.1. Installations Guidelines
• Install in horizontal pipework with test and drain plugs
downwards
- This position is best for draining
• Install shutoff valves
- Shutoff valves provide optimal serviceability
• Ensure good access
- Simplifies maintenance andinspection
Install right after water meter ifapplicable
- Protects against backflow from water systems
7.2. Assembly instructions
1. Thoroughly flushpipework
2. Close shutoff valve oninlet
3. Release pressure on outlet side (e.g. through watertap)
4. Close shutoff valve on outlet
5. Install check valve
• Note flowdirection
• Install without tension or bendingstresses
6. Slowly open shut off valves on inlet andoutlet