Herunterladen Diese Seite drucken
Danfoss Colibri ETS 12C Installationsanleitung

Danfoss Colibri ETS 12C Installationsanleitung

Elektrisches expansionsventil

Werbung

Installation guide
Colibri® Electric Expansion Valves
Type ETS 12C, ETS 24C, ETS 25C, ETS 50C, ETS 100C
Colibri® Electric Regulating Valves
Type KVS 2C, KVS 3C KVS 5C
Refrigerants : R410A, R404A, R507, R134a, R407A, R407B, R407C, R407F, R32, R290, R1234ze, R1234yf, R449A,
R449B, R452A, R1270, R600, R600a, R22, R23, R227, R417A, R444B, R447A, R448A, R454B, R422A, R422D, R427A,
R502, R513A, R413A, R438A, R450A, R455B, R454C, R454A, R452B and *L40
*R-number allocation by ASHRAE is pending
Allowable ambient temperature:
Min. -40 °C / -40 °F
Max. 70 °C / 158 °F
Stepper motor type:
Bipolar
Do not connect directly to AC/DC power source.
Connect valve to appropriate controller/driver only.
ETS / KVS Colibri® valves are delivered in open position, ready for brazing.
An AST –g service driver is available for manual operation / service of ETS / KVS Colibri® valves.
Flow direction
Reverse flow
Application ETS Colibri®
ETS Colibri®
Place the valve close to the evaporator.
It is recommended to use Danfoss filter drier before
the expansion valve or a strainer for particles of 150
micron or smaller.
© Danfoss | DCS (sw) | 2018.01
Downloaded from
www.Manualslib.com
Fluid temperature:
Min. -40 °C / -40 °F
Max. 70 °C / 158 °F
Phase current:
800 mA peak /
600 mA RMS
MADE IN DENMARK
Colibri® Electric
Expansion valve
Reverse
Normal
ETS XXXC
N0311A
10 Ω, 800mA peak
PS 50bar / MWP 735psig
-40/+70°C / -40/+158°F
034GXXXX
Bi-flow
Normal flow
(Using sight glass for flash gas detection - ETS 25C to ETS 100C)
KVS Colibri® valves have no sight glass integrated
manuals search engine
ENGINEERING
T O M O R R O W
Max. working pressure:
50 bar(g) / 725 psi(g)
Coil resistance:
Total steps:
10 Ω (20 °C / 68 °F)
600 full steps
GREEN:
DRY
YELLOW: WET
MADE IN DENMARK
Colibri® Electric
Expansion valve
ETS XXXC
N0311A
Reverse
Normal
10 Ω, 800mA peak
PS 50bar / MWP 735psig
-40/+70°C / -40/+158°F
034GXXXX
Application KVS Colibri®
Danfoss
Danfoss
R64-3051.10
R64-3051.10
English
KVS Colibri®
DKRCC.PI.VD1.F6.ML | 1

Werbung

loading

Inhaltszusammenfassung für Danfoss Colibri ETS 12C

  • Seite 1 Danfoss R64-3051.10 R64-3051.10 ETS Colibri® Place the valve close to the evaporator. It is recommended to use Danfoss filter drier before the expansion valve or a strainer for particles of 150 KVS Colibri® micron or smaller. DKRCC.PI.VD1.F6.ML | 1 © Danfoss | DCS (sw) | 2018.01 Downloaded from www.Manualslib.com...
  • Seite 2 PS 50bar / MWP 735psig -40/+70°C / -40/+158°F 034GXXXX Coil A = Coil B = 10 Ω (20 °C / 68 °F) Installation video DKRCC.PI.VD1.F6.ML | 2 © Danfoss | DCS (sw) | 2018.01 Downloaded from www.Manualslib.com manuals search engine...
  • Seite 3: Umgebungstemperatur

    ETS Colibri® Das Ventil direkt am Verdampfer montieren. Placez la vanne près de l’évaporateur. Es wird empfohlen Filtertrockner von Danfoss vor dem Expansionsventil oder einen Filter für Partikel von 150 µm oder kleiner zu verwenden. Il est recommandé d’utiliser un filtre déshydrateur Danfoss avant la vanne de détente, ou un filtre à...
  • Seite 4 Colibri® Electric Expansion valve ETS XXXC N0311A 10 , 800mA peak PS 50bar / MWP 735psig -40/+70°C / -40/+158°F 034GXXXX Installation Video Installation vidéo DKRCC.PI.VD1.F6.ML | 4 © Danfoss | DCS (sw) | 2018.01 Downloaded from www.Manualslib.com manuals search engine...
  • Seite 5 Danfoss R64-3051.10 R64-3051.10 ETS Colibri® Colocar la válvula próxima al evaporador. 阀关闭位置, 靠近蒸发器侧 Se recomienda utilizar un filtro deshidratador Danfoss antes de la válvula de expansión o un filtro para partículas de 150 micras o menores. 建议在膨胀阀前使用丹佛斯干燥过滤器或使用过滤目 KVS Colibri® 数小于等于150微米的过滤网...
  • Seite 6 Expansion valve ETS XXXC N0311A 10 , 800mA peak 在20℃时, 线圈A=线圈B=10Ω PS 50bar / MWP 735psig -40/+70°C / -40/+158°F 034GXXXX Instalación vídeo 安裝 視頻 DKRCC.PI.VD1.F6.ML | 6 © Danfoss | DCS (sw) | 2018.01 Downloaded from www.Manualslib.com manuals search engine...

Diese Anleitung auch für:

Colibri ets 24cColibri ets 25cColibri ets 50cColibri ets 100cColibri kvs 2cColibri kvs 3c ... Alle anzeigen