Dalap AP quiet PROFI 355-1 EC
Dalap AP quiet PROFI 400-1 EC
Dalap AP quiet PROFI 400V 450-3 EC
Dalap AP quiet PROFI 400V 500-3 EC
Dalap AP quiet 400V 500-4D
10V – 10 V DC power supply for a speed control potentiometer.
GND – DC power supply grounding.
E1 – 0-10 V input direct current signal for speed setting.
D1 – digital enable signal.
A1 – status / tacho output.
A – MODBUS communication interface (RS-285).
B – MODBUS communication interface (RS-285).
RC – NO-contact is closed in case of alarm (switching parameters: 250 V AC, 2 A).
PE – protective grounding.
N – power supply neutral.
L1 - power supply phase.
QF – circuit breaker.
R1/010 – speed controller.
24V – 24 V DC power supply.
10V – 10 V DC power supply for a speed control potentiometer.
GND – DC power supply grounding.
D1 – analogue input for speed setting compatible with 0-10 V signal or external potentiometer.
E1 – 0-10 V input direct current signal for speed setting.
RC – NO-contact closes in case of alarm (switching parameters: 250 V AC, 2 A).
PE – protective grounding.
L1, L2, L3 – power supply phase.
QF – circuit breaker.
R1/010 – speed controller.
R-1/010
R-1/010
Power
3~400 V 50 Hz
Power
1~230 V 50/60 Hz
Power
3~400 V 50/60 Hz
W1, W2, U1,U2, V1, V2 – contacts for motor
connection.
TW1, TW2 – motor thermal contacts.
PE – protective grounding.
L1, L2, L3 – power supply phase.
QF - circuit breaker.