Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Specification - Hautau RAZ K Montage- Und Betriebsanleitung

Rauchabzugszentrale
Inhaltsverzeichnis

Werbung

Technical specification

Power supply
Primary power supply
Secondary power supply
max. interrupt time
between power sources
Primary power supply
Mains supply voltage
System voltage
Power consumption
Terminal
Fuse
Secondary power supply
Battery pack
Type of battery pack
Emergency power supply
Quiescent current in Standby < 16 mA
Current output after 72 h
in emergency power supply DIN EN 12101-10
max. current output
Charging time
Terminal
Monitoring
Fuse
Output drives
Voltage
Ripple
Current (rated)
Load cycle
Current (short-time)
Opening-/Closing operation reversion of voltage polarity
Pulse off time during
reversion of polarity
Pulsing acc. to
prEN12101-9
Automatic clearing
Line monitoring
Terminal
Fuse
applicable for models
Voltage
Output, max. current load
Line monitoring
max. number
Emergency power supply
Fuse
Terminal
HAUTAU GmbH | Wilhelm-Hautau-Str. 2 | 31691 Helpsen | Germany | Tel +49 5724 393-0 | info@hautau.de | www.hautau.de
mains
battery pack
< 1 ms
230 V AC / 50 Hz
(-10% / +10%)
24 V DC (rated)
(18,0 V - 28,0 V)
170 W / Standby: 7,5 W
screw-type terminal 2,5 mm²
T 500 mA / 250 V
2 x 12 V / 2,6 Ah
lead, dim. 70 x 48 x 98 (mm)
72 h
4 A for 180 s acc. to
4 A
24 h
flat plug 4,8 mm
yes, cyclic approx. every 300 s
T 5,0 A / 250 V
24 V DC (rated)
(18,0 V - 28,0 V)
< 5%
4 A
4 min. / 4 A;
16 min. / 0,3 A (ventilation is
blocked)
5,8 A (for < 10 ms)
approx. 2 s
yes, every 2 minutes
Open / Close in ventilation mode
after 3 min
yes, until the last conduit box by
monitoring diodes with 3rd line
screw-type terminal 2,5 mm²
T 5,0 A / 250 V
Fire pushbutton
HAUTAU FR 900 ..
120 mA
yes
10
yes
Potential-free contacts
SHEV activation
Collective fault
Material and mechanical characteristics
dim.; B x H x T (mm)
Housing
Colour
Non-halogen
Silicone-free
RoHS compliant
Connection and operation
applicable for SHEV
applicable for ventilation
Ventilation function
in case of mains failure
Service
Change of battery packs
Installation and environmental conditions
Nominal temperature
Ambient temp. range
Installation situation
applicable for
outdoor installation
Protection system
Approvals and certificates
Controlling equipment
Power supply
CE compliant
RoHS compliant
Protection class
Outputs
automatic detectors
Ventilation pushbutton
RM 523 and TM 523
HAUTAU LT, LTA and
double rocker switch
24 V DC (rated) (19,3 V - 28,0 V)
120 mA
yes
10
yes
electronic
screw-type terminal 2,5 mm²
changeover contact, max. 30 V / 1 A
changeover contact, max. 30 V / 1 A
metal sheet housing 302x302x115;
PVC AP 287 x 236 x 112;
PVC UP 283x232x70 (112)
metal sheet for AP installation;
PVC (material) for AP und UP
installation
metal sheet: grey; PVC: white
yes
yes
yes
yes
yes
no, ventilation blocked
once a year
every 4 years and in case of
fault function
20 °C
-5 °C to +40 °C
dry
no
IP 30 (acc. to DIN EN 60529)
certified by TÜV based on
prEN 12101-9
certified by TÜV acc. to
EN 12101-10
yes, acc. to EMC Directive
2004/108/EG and Low-voltage
Directive 2006/95/EG
yes, acc. to Directive 2011/65/EG
class I
Wind-/Rain sensor
HAUTAU WG/H,
REM/H and WREM/H
120 mA
400 mA
no
10
no
T 400 mA / 250 V
no
1
no

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis