Technical Data - Siemens 2M Hinweise Für Den Einsatz

Kommunikationsumsetzer

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

English

Technical Data

Auxiliary voltage
Voltage supply via extended range power supply unit
DC voltage
Rated auxiliary voltage U
Permissible voltage range
Max. power input
Permissible AC ripple voltage,
Peak to peak
Stored energy time in the event of power
failure / short circuit of the auxiliary voltage
AC voltage
Rated auxiliary voltage U
Permissible voltage range
Max. power input
Alarm relay (GOK/DR)
Contact
Switching capability
Switching voltage
Permissible current per contact
Interface to the protection device
Optical fibre
– Fibre–optic plug type
– Optical wavelength
– Laser class 1 acc. to EN 60825–1/–2
Transmitting power (peak)
50/125 µm, NA
62.5/125 µm, NA
52
Downloaded from
www.Manualslib.com
DC
N
AC
N
MAKE
BREAK
1)
= 0.2
1)
= 0.275
manuals search engine
DC 24 V to DC 250 V
DC 19 V to DC 300 V
approx. 1.8 W at DC 24 V
≤ 12 % at rated voltage, IEC 60255–11
≥ 50 ms
AC 115 V to AC 250 V, 50/60 Hz
AC 92 V to AC 286 V
approx. 4.5 VA at AC 230 V
1 change over contact
1000 W/VA
30 VA
40 W resistive
250 V
5 A continuous
30 A for 0.5 s
ST–plug
λ = 820 nm
for use of G62.5/125 µm or G50/125 µm
min.
type
-19.8 dBm
-15.8 dBm
-16.0 dBm
-12.0 dBm
7XV5662-0AD00
max.
-12.8 dBm
-9.0 dBm
C53000-B1174-C205-1