5.3.1
Power supply control unit
Verify that the product is connected to mains by means of a suitable,
permanently installed cable (for example NYM-J 3 x 1.5 mm²).
Verify that the power supply to the control unit is separately fused (16 A
maximum).
1. Route the mains cable through the left cable gland into the control unit.
2. Connect the phase to terminal L1 and the neutral conductor to
terminal N.
- The protective ground conductor (PE) does not have to be connected.
1
3
Fig 5: Electrical connection
5.3.2
Connecting the floating probe
1. Install the probe cable.
2. Route the probe cable through the cable gland at the right to the termi-
nals designated "Sonde".
3. Connect the two wires. Any polarity is permissible.
Mounting
2
4
J1
1. Mains fuse F1
2. Relay fuse F2
6
3. Supply voltage
4. Relay for additional equip-
ment
5. Floating probe
6. Slot for EnOcean® wire-
less module
J1 jumper