Energy meter 125A

direct connection, MID

4. PREPARATION - CONNECTION

Fixing:
On symmetrical EN/IEC 60715 rail or DIN 35 rail.
Operating position:
Vertical,
Horizontal,
Terminals:
- Terminals depth: 8mm
- Stripping length: 8mm
Terminal protection
:
- Voltage terminals are protected with integrated sealable screw
cover.
Wiring diagram:
3
6
9
L1
L2
L3
L1
L2
L3
N
11
1
4
7
L1
L2
L3
N
Technical data sheet: IDP000186EN_02
Upside down,
On the side
Updated: 15/06/2018
Codes: CE6DMID52 – CE6DMID56
4. PREPARATION - CONNECTION
Screw head:
- Voltages connection terminals (L1, L2, L3): Slotted and Pozidriv
- Neutral connection terminal (N): Slotted
- Terminal blocks in the upper part of the meter (input, pulse output
and RS485 bus): Slotted
Recommended tightening torque:
- Voltages connection terminals (L1, L2, L3): 3 Nm
- Neutral connection terminal (N): 1 Nm
- Terminal blocks in the upper part of the meter (input, pulse output
and RS485 bus): 0,2 Nm
Max. tightening torque:
- Voltages connection terminals (L1, L2, L3): 4 Nm
- Neutral connection terminal (N): 1,2 Nm
- Terminal blocks in the upper part of the meter (input, pulse output
and RS485 bus): 0,3 Nm
Tools required:
- Voltages connection terminals (L1, L2, L3):
Flat screwdriver 6 mm or Pozidriv PZ2
- Neutral connection terminal (N):
Flat screwdriver 4 mm
- Terminal blocks in the upper part of the meter (input, pulse output
and RS485 bus): Flat screwdriver 2,5 mm
- For fixing the device on the DIN rail: Flat screwdriver 5.5 mm (from
4 to 6 mm).
Connectable section:
- Copper cables.
- Voltages connection terminals (L1, L2, L3):
Without ferrule
Rigid cable
1 x 4 ÷ 50 mm²
Flexible cable
1 x 4 ÷ 35 mm²
ATTENTION: for safety reasons, it is compulsory not to exceed 4
A/mm
as current density in the input terminals
2
- Neutral connection terminal (N):
Without ferrule
Rigid cable
1 x 4 ÷ 16 mm²
Flexible cable
1 x 4 ÷ 16 mm²
- Terminal blocks in the upper part of the meter (input, pulse output
and RS485 bus):
Without ferrule
Rigid cable
1 x 0,2 ÷ 1,5 mm²
Flexible cable
1 x 0,2 ÷ 1 mm²
Created: 02/05/2018
With ferrule
-
1 x 4 ÷ 35 mm²
With ferrule
-
1 x 4 ÷ 16 mm²
With ferrule
-
1 x 0,2 ÷ 1 mm²
2 / 5