INSTRUCTION
MR32W
IN20023 REV.B , 2019-06-19
Caution! Read and understand the instruction before using the product.
Caution! Ensure that the installation complies with local safety
regulations.
Caution! Before installation or maintenance, the power supply should
first be disconnected. Installation or maintenance of this unit should only
be carried out by qualified personnel. The manufacturer is not responsible
for any eventual damage or injury caused by inadequate skills during instal-
lation, or through removal of or deactivation of any security devices.
Technical Data
Supply voltage
24 V AC/DC (21...27 V AC/DC)
Frequency
868 MHz
Protection class
IP54
Ambient temperature
-10...+50 °C
Ambient humidity
Max. 85 % RH, non-condensing
Dimensions, external (WxHxD)
120 x 112 x 40 mm
Internal serial port, type
RS485, isolated
Internal serial port, built-in protocol
Modbus
Internal serial port, communication
1200 / 2400 / 9600 (default) / 19200 /
speed
38400 /57600 bps
MR32W
Internal serial port, parity
None (default) / even / odd
Internal serial port, stop bit
1 stop bit (default) / 2 stop bit
Installation
1. Lift the lid to access the terminals.
2. Connect the receiver to the master controller via the RS485 terminal.
3. Connect the receiver to the supply voltage. The display will beep once
and two small LED lights will start blinking on the display.
4. Mount the receiver on any flat surface. If it is installed in a humid
environment, vertical mounting is recommended.
When the receiver is powered on it will automatically forward signals
received from the paired sensors and detectors to the controller.
Wiring
1
4
2
GND A- B+
G0
Number
Description
1
Display
2
Joystick with Menu button
3
Supply voltage terminal
4
RS485 terminal
Settings
The joystick is used to manoeuvre through the channels (see Table 1). For
each selected channel four different values are shown subsequently in the
display:
1. Current channel, e.g. 01
1
2. Received signal strength indicator (RSSI), S.1...9
S. = signal strength, 1 = weak signal, 9 = strong signal
S.- = no sensor is paired on the selected channel
Note that the signal strength abbreviation S. should not be mistaken
for number 5.
3. Value 1 for the sensor or detector (if available), 0...99. If both value 1
and 2 are available, value 1 always shows the temperature.
4. Value 2 for the sensor or detector (if available), 0...99. Value 2 can for
example show the humidity.
Table 1 Navigate the channels
Description
Activate the display
Move to the subsequent channel.
Move to the preceding channel.
Jump 8 channels forward.
Leave the menu and inactivate the display.
Many default settings can be changed via the display. The joystick is used to
navigate within the menu as shown in Table 2. To enter the menu, press the
Menu button 4 s when the display is inactive. Six levels are available:
1. A: Pair and unpair sensors
3
2. B: Modbus addresses, as hexadecimal numbers
3. C: Communication speed (baud rate)
G
4. D: Parity and stop bit
5. E: Selected frequency
6. F: Current software version
Table 2 Navigating the menu
Description
Enter into the menu
Move between the different levels in
the menu (A-F)
Enter into one level
Move between different values within
one level
Leave the menu and inactivate the
display.
A complete description on how to read and modify the settings, both via the
display and via Modbus, can be found in the Modbus variable list.
Manoeuvre
Time
Press the Menu
1 s
button
Push UP
1 s
Push DOWN
1 s
Push RIGHT
1 s
Push LEFT
3 s
Manoeuvre
Time
Press the Menu button when
4 s
the display is inactive
Push UP or DOWN
1 s
Press the Menu button
1 s
Push UP or DOWN
1 s
Push LEFT
3 s

Werbung

loading

Inhaltszusammenfassung für Industrie Technik MR32W

  • Seite 1 Internal serial port, parity None (default) / even / odd 2. Received signal strength indicator (RSSI), S.1…9 MR32W S. = signal strength, 1 = weak signal, 9 = strong signal Internal serial port, stop bit 1 stop bit (default) / 2 stop bit S.- = no sensor is paired on the selected channel...
  • Seite 2: Installazione

    Pairing and unpairing ISTRUZIONI PER L'INSTALLAZIONE MR32W Cablaggio The receiver can pair up to 32 sensors and detectors. This can be done either manually via the menu or via Modbus communication. To pair and unpair via Modbus communication, see the Modbus variable list.
  • Seite 3: Technische Daten

    INSTALLATIONSANLEITUNG Passaggio al canale successivo. Premere UP (SU) comunicazione Modbus. Per associare e annullare l'associazione tramite la MR32W comunicazione Modbus, leggere l'elenco variabili Modbus. Passaggio al canale precedente. Premere DOWN (GIÙ)
  • Seite 4: Bedienung

    3. Wert 1 des Fühlers/Melders (Falls vorhanden), 0...99. Stehen Wert 1 und Werte von den Fühlern/Meldern. Wert 2 zur Verfügung, dann ist Wert 1 immer eine Temperatur. 4. Wert 2 des Fühlers/Melders (Falls vorhanden), 0...99. Wert 2 könnte z.B. die Feuchtigkeit anzeigen. MR32W...
  • Seite 5 Sauter 8 canaux vers l'avant Pousser à droite INSTRUCTION MR32W Quitter le menu et désactiver l’écran Pousser à gauche Raccordement De nombreux réglages par défaut peuvent être modifiés via l’écran. La manette permet de naviguer dans le menu tel que décrit dans le Tableau 2.
  • Seite 6 Ce produit porte le marquage CE. Pour plus d'information, veuillez consulter le site web www. industrietechnik.it. Contact AB Industrietechnik Srl, Via Julius Durst 50, 39042 Bressanone (BZ) Tel: +39 0472 83 06 26, Fax: +39 0472 83 18 40 www.industrietechnik.it, info@industrietechnik.it MR32W...