GB
The DALI-Gateway identifies the replaced DALI device and down-
loads the required data into the device. The display shows ‚LE'.
Simultaneous replacement of several DALI devices only with
commissioning software and project data.
Manual control with keypad not possible
Cause 1: manual control mode not programmed.
Reprogram the device, activate the manual control.
Cause 2: manual control disabled via the bus.
Enable the manual control mode.
DALI group control not possible
Cause: DALI group disabled via the bus or via manual control.
Re-enable the output.
50
Help in case of trouble