Relative humidity
5.
CONNECTING SA-CONTROL REMOTE CONTROLLER
TO AN AIR HANDLING UNIT
Use the following steps to connect a SA-Control remote controller to an air han-
dling unit:
• Unpack the SA-Control remote controller;
• Connect the cable to the connector slot on the control panel pic. 3.1 - 3.3 (page
63):
• Use the cable with an RJ10 connector for the connection to the air handling unit
with PRV control board (further RJ10 cable) pic. 4.1 (page 63);
• Use the cable with an RJ45 connector for the connection to the air handling unit
with a MCB or mini MCB control board (further RJ45 cable) pic. 4.2 (page 63).
• Plug in the RJ45 cable connector to the X18 MCB pic. 5 (page 63) or X18 mi-
niMCB pic. 6 (page 64) connection slot on the control board. Make sure that the
XQLW LV VZLWFKHG R GXULQJ WKH RSHUDWLRQ ,I WKH YHQWLODWLRQ XQLW LV HTXLSSHG ZLWK D
PRV control board, plug the RJ10 cable connector into the RS485_2 slot on the
HTXLSPHQW FDVLQJ pic 7 (page 64);
• Plug the ventilation unit into the electric circuit.
6.

INSTALLATION ON A WALL

• Turn the panel ¿J  (page 63).
• Put it at the desired location on the wall pic. 8 - 11 (page 64). Mark the positions
of the mounting holes.
• Drill two 5 mm holes at the marked positions for the nylon plugs and the hole
throughout the wall to install the cable pic. 9 (page 64). Insert the nylon plugs.
NOTE: You can use special metal plugs (included) instead of the nylon ones.
• Use the included 2.9x16 DIN7981C screws and mount the panel to the wall as
indicated in ¿J  (page 64).
• Put the panel on the mounting bracket ¿J    (page 64).
IMPORTANT: IT IS FORBIDDEN to leave the remaining remote controller's
cable in the AHU's control box pic. 12 (page 64)!
IMPORTANT: Do not forget to connect the cable before attaching the panel.
7.
THE MAIN SCREEN PRV BOARD
In pic. 13 (page 65) the main window of the PRV board functions is shown:
l1. Date and time.