USER'S MANUAL: INSTRUCTIONS AND WARNINGS
The smoke vent control panel EFC 4 A allows to control the windows opening or closing by 24 VDC actuators
using an opening/closing operation with polarity inversion.
Opening and closing operation can be controlled as follows:
-
For emergency by smoke detectors (Part No. 36418Q) or an emergency pushbutton (Part No 40564B)
-
For ventilation by a standard button (Part No 41013B or similar).
The emergency push-button Part No 40564B is recommended to signal the EFC control panel conditions when
the panel itself is installed in a not visible position.
Obviously the emergency command has priority over ventilation (manual opening and closing are disabled).
The actuators are fed directly by a power supply unit; the batteries are used in case of voltage supply failure only.
WARNING:
read the instruction manual carefully before assembling
keep this manual also after installation for any further issue
uncorrect or improper installation may cause failure of the system and/or injury to things or people
electrical connections must carried out by qualified people only
turn the power off before opening the control unit

TECHNICAL DATA

Dimensions LxHxD: mm. 196 x 246 x 98
Voltage supply: 230 VAC (or 115 VAC version)
Nominal current: 4 A
Visual signals:
3 GREEN, YELLOW, RED leds to verify the state through the
front opaque cap
Acoustic signals: output for sel-fed alarm siren
Outputs:
-
2 outputs for 24 VDC motors, with polarity inversion,
maximum load 2 Amps each
-
1 siren/relay output
Inputs:
-
1 input for smoke detectors
-
2 inputs for manual control of the 2 groups of actuators
-
1 input for the emergency pushbutton
Equipment:
-
Nr. 2 x 12 V, 4 Ah batteries (*)
-
Nr. 10 extractable connectors for easy connections
-
Nr. 6 pre-drilled holes for PG9 cable clamps
-
Nr. 1 air intake for the ventilation of the panel
Batteries recharging time: 10 hours
(*)If the batteries are not supplied from UCS, see the wiring connections at pag. 16
Doc. 82831O – Rev. 24/11/08