7. Commissioning
The device can be operated either using
batteries or a power supply unit.
7.1 Insert batteries
1. Loosen fastening screws
2. Open housing cover
3. Insert batteries
4. Close housing cover
5. Tighten fastening screws
7.2 Connect power supply unit
1. Insert plug on back of housing
2. Insert power supply plug
7.3 Functional check
After applying supply voltage, a reverse rinsing is trig-
gered. The desired reverse rinsing interval can then be
set.
7.4 Set the reverse rinsing interval
The reverse rinsing interval can be set to 8
different intervals
The selection of the interval depends on the
degree of soiling of the water.
Setting
Interval
OFF
0
TEST
Test
1h
1 hour
1d
1 day
6d
6 days
15d
15 days
30d
30 days
45d
45 days
2M
2 months
3M
3 months
1. Turn setting knob to the desired reverse rinsing
interval
o Selection is confirmed by the flashing frequency
of the LED
o Directly after setting the reverse rinsing interval,
an automatic reverse rinsing is triggered

10. Troubleshooting

Problem
LED flashes
No reverse rinsinging
Honeywell GmbH
GB
LED display (flashes)
1x
2x
3x
4x
5x
6x
7x
8x
9x
10x
Cause
Batteries too weak
Batteries too weak
Power supply not plugged in
Power supply unit defective
Ball valve in filter defective

8. Maintenance

Battery display
LED – flashes when voltage is under 3.6V
8.1 Batteries
The batteries must be replaced after no more
than 12 months
It is recommended to use high quality, long life
(AA) batteries.
1. Loosen fastening screws
2. Open housing cover
3. Insert batteries
4. Close housing cover
5. Tighten fastening screws
8.2 Ball valve
Check regularly that the drain ball valve can
move freely.
8.3 Cleaning
Use only cold, clear drinkink water to clean the
synthetic material surfaces.
9. Disposal
• High quality synthetic material housing
WEEE 2002/96/EC.
Remedy
Replace batteries
Replace batteries
Plug in power supply
Replace power supply unit
Replace ball valve