Electrical And Wiring; Electrical Data; Caution; Recommended Fuse And Cable Sizes - McQuay R410A INVERTER SERIE Installationsanleitung

Vorschau ausblenden Andere Handbücher für R410A INVERTER SERIE:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 30
Do not allow water to remain in the water pipes if the unit is not operating for a long period.
Water must be drained out if the unit is not running during winter. Failing to do so would cause the pipe to crack.
Do not drink the chilled water in the unit.
Refer to the wiring diagram provided on the unit when making electrical wiring.
Do not ground any electrical equipment to the water piping.
Install an external isolator switch (if it is not provided) to prevent electrical shock.
Table B-1 : ( R410A - Heatpump )
Model
Power Supply
Voltage range
Nominal Power Input (Cooling/Heating)
Nominal Current Input (Cooling/Heating)
Compressor Full Load Current (FLA)
Rotor Locked Current (Comp 1/2)
Pump Power Input (max speed)
* Reading taken at rated compressor frequency. The power input and current differ depending on the combination of outdoor
temperature and entering water temperature. For further detail, please refer to technical manual.
Model
Voltage Range **
Recommended Fuse *
Power Supply Cable Size *
Number of Conductor
Interconnection Cable Size *
IMPORTANT : * The figures shown in the table are for information purpose only. They should be checked and selected to
comply with the local/national codes of regulations. This is also subjected to the type of installation and
conductors used.
** The appropriate voltage range should be checked with label data on the unit.
All field wiring must be installed in accordance with the national wiring regulation.
All the terminals and connections must be tightened. Improper connection and fastenings could cause electric shock,
short circuit and fire.
Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring work
according to the wiring diagram.
The unit must be GROUNDED to prevent possible hazards due to insulation failure.
All electrical wiring must not touch the refrigerant piping, compressor, pump, fan motor or any moving parts of
the fan motors.
Do not operate the chiller with wet hands. It would result in electric shock.
Do not use fuse of different amperage than stated. Using wire etc. to replace a fuse could cause equipment damage
or fire.

! ! ! ! ! CAUTION

ELECTRICAL AND WIRING

ELECTRICAL DATA

V-ph-Hz
V
kW
A
A
A
W

RECOMMENDED FUSE AND CABLE SIZES

5ACV30CR
A
2
mm
mm
2
! ! ! ! ! CAUTION
1-3
5ACV30CR
230 / 1 /50
220 / 240
5.3 / 4.5
26.6 / 21.5
25.9
-
200
5ACV55CR
230 / 1 /50
415 / 3 /50
36
10
3
1.5
5ACV55CR
5ACV75CR
415 / 3 /50
415 / 3 /50
380 / 415
380 / 415
7.6 / 6.1
9.1 / 7.9
16.1 / 14.0
16.6 / 15.4
18.6
18.6
-
-
700
800
5ACV75CR
415 / 3 /50
25
36
10
10
5
5
1.5
1.5