1.3.2 Setting range of the motor-protective circuit-breaker

1 Motor-protective circuit-breaker PKE12, PKE32 and PKE65
L1 L2 L3
-Q1
I > I > I >
T1 T2 T3
Figure 3: Circuit diagram for PKE motor-protective circuit-breaker with
trip block PKE-XTU(W)(A)-...
PKE motor-protective circuit-breakers need to be matched to the
corresponding rated motor current by using the setting dial (→ Figure 4).
...A
Figure 4: Setting dial for rated motor current
Three basic devices (PKE12 for up to 12 A, PKE32 for up to 32 A, and PKE65
for up to 65 A) and six different electronic trip blocks make it possible to
monitor motors with a rated motor current range of 0.3 to 65 A (→ table 1).
The rated operational current and the tripping class must be set on all trip
blocks PKE-XTU(W)(A)-...
In addition, PKE-XTU(W)A-... trip blocks can be used to transmit operational
data (such as instantaneous current values and trip reasons) to a higher-level
field bus system via SmartWire-DT. These communication tasks do not
affect the device's motor protection function in any way.
For more information, please consult the manual
MN05006001Z-EN (previously AWB2723-1613).
It is availalbe for download on the Internet.
http://www.eaton.de/EN/EatonDE/ProdukteundLoesungen/Electrical/
Kundensupport/DownloadCenter/index.htm
→ Customer support → Download Center –
Documentation
PKE12, PKE32, PKE65 11/17 MN03402004Z-DE/EN www.eaton.com
1.3 Description of device
CLASS
31