Herunterladen Diese Seite drucken

LMF Clima LCE Bedienungsanleitung Seite 13

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Light Electronic Control LCE User Manual
16413 Profile 1: Set Heat Band 2
16414 Profile 2: Set Heat Band
Monday Profile Selection
16415
1 = P1; 2 = P2; 3 = P3; 4 = P4
Tuesday Profile Selection
16416
1 = P1; 2 = P2; 3 = P3; 4 = P4
Wednesday Profile Selection
16417
1 = P1; 2 = P2; 3 = P3; 4 = P4
Thursday Profile Selection
16418
1 = P1; 2 = P2; 3 = P3; 4 = P4
Friday Profile Selection
16419
1 = P1; 2 = P2; 3 = P3; 4 = P4
Saturday Profile Selection
16420
1 = P1; 2 = P2; 3 = P3; 4 = P4
Sunday Profile Selection
16421
1 = P1; 2 = P2; 3 = P3; 4 = P4
Profile Enabled
16422
0 = Off; 1 = On
16423 Antifreeze Setpoint (rev 2.1)
16424 Antifreeze Differential (rev 2.1)
Address
Description
read
Input-Output
State On-Off digital input (DI1)
8192
0 = On; 1 = Off
8960 Regulation Sensor Temperature
Current Fan Speed
8961
0 = Off; 1 = Min; 2 = Med; 3 = Max
Three Point Cold or Changeover
8962
Valve Estimated Position
Three Point Hot Valve Estimated
8963
Position
Heater Status
8964
0 = Off; 1 = On
External Bypass Status
8965
0 = Off; 1 = On
8966 Fresh Air Temperature
8968
On Off Status
0= Not Active
Address
Description
1= Active
read
Allarm
2=Manual Reset
9000 Suplpy Air Sensor Error
9001 Fresh Air Sensor Error
9002 SKW Display Sensor Error
9003 Filter Alarm
Heater Overheating Alarm
9004
(Manual Reset)
9005 Antifreeze Alarm (rev 2.1)
Address
Description
read
Version
9471 Application version
Note:
(divided 10, °C) divide the value by 10, the result is in degree Celsius with one decimal place (Es: 175= 17.5°C)
(divided 10, %) divide the value by 10, the result is in percentage with one decimal place (Es: 505= 50.5%)
(HH:MM) minutes starting from midnight where 0= 00:00 e 1439= 23:59 (In example: 120= 02:00; 1170= 19:30)
Light control manual-ENG-neutro_03.docx
20.0
°C
200
20.0
°C
200
1
1
1
1
1
1
1
1
1
1
2
2
4
4
0
0
5.0
°C
50
1.0
°C
10
Value
Um
Default
0
0
17.5
°C
0
0
0
0.0
%
0
0.0
%
0
0
0
0
0
11.2
°C
0
0
0
Value
Um
Default
0
0
0
0
0
0
0
0
0
0
0
0
Value
Um
Default
2.1
21
Rev. 04
firmware 2.4
50
Profile 1: Set Cool Band 2
50
Profile 2: Set Cool Band
1
4
1
4
1
4
1
4
1
4
1
4
1
4
0
1
-50
150
1
50
Min
Max
0
1
-500
1100
0
3
0
1000
0
1000
0
1
0
1
-500
1100
0
1
Min
Max
0
1
0
1
0
1
0
1
0
2
0
1
Min
Max
EN
EN 6 / 6