Herunterladen Diese Seite drucken

GCX PolyMount Anwendungen-Installationsanleitung Seite 2

Wandprofil für nicht-erdbebenanfällige

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 7
®
PolyMount
PLAN
3.49 CM
C-STUD
GCX CHANNEL
TOP TRACK
4" X 1½" (10.16 x 3.81 CM) 16
GAUGE TRACK FROM
FLOOR TO FINISH CEILING
#10 SHEET METAL
SCREW S THRU 9/64"
(3.57 mm) DIA. HOLES
OR #28 (3.5 mm) DRILL
@ 18" (45.72 CM) O/C
EA. SIDE
C-STUDS FROM
FLOOR TO FINISH
CEILING. INSERT
BETWEEN REG.
WALL STUDS OR
ADD ONE L OR R
OF EXISTING
ROOM WALL STUD.
LAYOUT TO
OBTAIN DESIRED
LOCATION OF
CHANNEL.
BOTTOM TRACK
ELEVATION
4" X 1 ½"(10.16 x 3.81 CM)
16 GAUGE TRACK FROM
FLOOR TO FINISH CEILING
10.16 CM
#10 SHEET METAL
SCREWS THRU 9/64"
(3.57 mm) DIA. HOLES
OR #28 (3.5 mm)
8.89 CM
DRILL @ 18" (45.72
CM) O/C EA. SIDE
GYPSUM BOARD
INSTALL ONE-#10
SMS ON EXACT
CENTERLINE OF
TRACK PRIOR TO
GYPSUM BOARD
COVER IN ORDER TO
LOCATE SAME FOR
INSTALLATION OF
CHANNEL AS
DIMENSIONS ARE
CRITICAL
SUPPORT BACKING FOR 5/8 (15.87 mm) GYPSUM BOARD
WALLS FOR WALL MOUNTED INSTRUMENTATION.
THE MAXIMUM LOAD RATING FOR THIS SYSTEM IS 80 lbs. / 36 Kg
(VB SERIES PRODUCTS) OR 110 lbs. / 50 Kg (FT SERIES PRODUCTS)
THIS ANCHORAGE WILL ALLOW FOR A QUICK AND SIMPLE INSTALLATION
OF THE WALL CHANNEL. 16 GAUGE STEEL WILL PREVENT THE MATERIAL
FROM EXTRUDING UP THE SHANK OF THE SCREW (STRIPPING). 11/64"
(4.36 mm) DIAMETER HOLES ARE REQUIRED FOR #12 X 2-3/4" HIGH
TENSILE, PHILIPS HEAD SCREWS (4) INSTALLED DOWN THE CENTERLINE.
(NON-SEISMIC APPLICATIONS).
A SECOND TRACK CAN BE USED FOR BACK TO BACK INSTALLATIONS. A
2" X 4" (5.08 x 10.16 CM) WOOD STUD MAY BE USED IF ALLOWED BY LOCAL
BUILDING CODES.
MINIMUM REQUIREMENT
16 GAUGE STEEL STUD
2" X 4" (5.08 x 10.16 CM) WOOD STUD
A LATERAL FORCE IN EXCESS OF 80 LBS. (36 Kg) APPLIED 17" (43.18
CM) OUT FROM THE WALL WILL CRACK 5/8" (15.87 mm) THICK GYPSUM
BOARD ALONG THE CHANNEL FLANGE. THIS IS NOT ACCEPTABLE IN
SEISMIC SENSITIVE AREAS AND NOT ALLOWED IN CALIFORNIA.
SEISMIC WALL CHANNEL INSTALLATION INSTRUCTIONS ARE PRINTED
SEPARATELY.
DU-WC-0001-I-20 Rev B 1/7/00 Page 2 of 28