Valve actuator for 3-position control
RVAR5-230 fits valve series MMV/MMR. The actuator can be set
manually.
Technical data
Supply voltage
230 V AC ±15 %, 50 Hz
Control signal
3-position
Power consumption
Max. 12 W
Stroke
10...30 mm
Stroke time
3 s/mm
Force
500 N
Ambient temperature
0...50ºC
Storage temperature
-40...80°C
Ambient humidity
10...90 % RH
Dimensions
200 x 310 x 135 mm
Protection class
IP54
Mounting
If the valve stem lock and valve throat adaptor are not already
mounted on the valve, mount them. Pull the valve stem out as far as
possible.
Remove the locking bolts and U-bolt from the actuator yoke.
Depress the spring-loaded tab on the drive rod coupling device and fit the
valve stem into the coupling. Release the tab to connect the valve to the
actuator.
The position of the yoke on the valve stem adaptor must be adjusted so
that the U-bolt mounting holes line up with the groove in the valve throat
adaptor. If the drive rod needs to be moved in or out for this, depress the
central button of the control knob and turn it clockwise to extend the drive
rod and counter-clockwise to retract it (see Manual override).
Mount the U-bolt and the nuts. Tighten the nuts until the actuator is firmly
attached. Disassembly takes place in reverse order.
Mounting positions
90º
90º
Wiring
Y1
Y2
N
1
2
3
Y1 circuit closed = Actuator spindle
is extending from the actuator
Y2 circuit closed = Actuator spindle
is retracting into the actuator
L
N
230V AC
Calibration
Field calibration is not required. When the valve reaches an end position
and the actuator provides nominal positioning force, power to the actuator
RVAR5-230
motor is cut automatically.
Manual override
To manually set the valve position, first depress the central part of the
knob until it clicks in place and remains depressed (1 in the figure).
The valve position may then be changed manually by turning the
knob (2 in the figure). Clockwise rotation will extend the drive rod and
anti-clockwise rotation will retract it.
To return to normal operation, position the knob so that it is in line with
the text (Auto) on the cover. Then press down on the outer parts of
the knob (3 in the figure). The depressed central part will pop out and
the actuator will return to operation.
Low Voltage Directive (LVD) standards
This product conforms to the requirements of the European Low Volt-
age Directive (LVD) 2006/95/EC through product standards EN60730-
1:2000 and EN60730-2-14:1997.
EMC emissions & immunity standards
This product conforms to the requirements of the EMC Directive
2004/108/EC through product standards EN60730-1:2000 and
EN60730-2-14:1997.
RoHS
This product conforms to the Directive 2011/65/EU of the European
Parliament and of the Council.
Contact
AB Regin, Box 116, 428 22 Kållered, Sweden
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50
www.regin.se, info@regin.se
1

Werbung

loading

Inhaltszusammenfassung für Regin RVAR5-230

  • Seite 1 Valve actuator for 3-position control age Directive (LVD) 2006/95/EC through product standards EN60730- 1:2000 and EN60730-2-14:1997. RVAR5-230 fits valve series MMV/MMR. The actuator can be set manually. EMC emissions & immunity standards This product conforms to the requirements of the EMC Directive...
  • Seite 2 RVAR5-230 90º 90º Läs denna instruktion innan produkten monteras och ansluts Ventilställdon för 3-punktsstyrning RVAR5-230 passar till ventilserien MMV/MMR. Ställdonet kan köras manuellt. Inkoppling Tekniska data Matningsspänning 230 V AC ±15 %, 50 Hz För att manuellt ställa in ventilpositionen, tryck först ned mittknap-...
  • Seite 3 90º 90º Diese Anleitung vor Montage und Anschluss des Produktes bitte durchlesen Ventilstellantrieb mit 3-Punkt-Stellsignal Der Ventilstellantrieb RVAR5-230 ist für die Ventilserie MMV/MMR vorgesehen. Der Stellantrieb kann manuell verstellt werden. Anschluss Technische Daten Versorgungsspannung 230 V AC ±15 %, 50 Hz...
  • Seite 4 Veuillez lire cette instruction avant de procéder à l’installation et au raccordement de l’appareil. Moteur de vanne pour signal de commande 3 points L’actionneur RVAR5-230 est prévu pour le pilotage des vannes appar- Raccordement tenant à la gamme MMV/MMR. Il dispose d’une commande manuelle. Caractéristiques techniques Pour régler manuellement la position de la vanne, appuyez sur la...

Diese Anleitung auch für:

Rvar10-230Rvan5-230