Installation Rules
The beam and the reflector must be installed on plane wall, not subject to vibrations or deformation.
Please keep in mind these basic rules:
-
distance between the beams (D)
must be between min 10 and
max. 18 meters.
-
distance from the walls
must be about the half of
the distance between
two beams (1/2 D).
-
distance from the ceiling
(H) must be between min. 40
cm. and max 1 meter.
-
check the possibility of installing
reflectors in axis with beams.
E
N
G
1 mt
T X /
RX
In case of sloping roofs, install the first beam at H
distance from the highest side of the roof.
Install other beams maintaining distance D
between them and distance H from the ceiling.
Check to have the max distance of 1/2D
between the beam and the wall from the
lowest side of the roof.
Check the possibility of installing
reflectors in axis with beams.
In case of inclination of the roof, install the first beam at about 1 meter
D
from the highest wall and at H distance from the ceiling.
D
T X /
RX
1/2 D
1/2 D
H
T X /
RX
Install other beams maintaining distance D between
them and distance H from the ceiling.
Check to have max 1/2 D distance
between the beam and the lowest
1/2 D
T X /
RX
T X /
RX
D
- 18 -
D
T X /
RX
side of the wall from the ceiling.
Check the possibility of
installing reflectors in axis with
beams.
H
T X /
RX
T X /
RX
D
IST0570V3.1