Herunterladen Inhalt Inhalt Diese Seite drucken

Transportation And Storage; Safety Precautions - Salda AVA series Montage-Und Installationsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 14
1. SYMBOLS AND MARKING
1 - Logo; 2 - Product code (SKU); 3 - Product name; 4 - Technical data; 5 - Lot number and production date; 6 - Production place.

2. TRANSPORTATION AND STORAGE

Units are packed in the factory to complay needs of normal transportation handling. Use suitable lifting and moving equipment when handling units
in order to prevent damages and injuries. Do not use cables, terminal boxes, and inlet-exhaust flanges for lifting and moving units. Avoid hits and
shock loads. Units should be stored in dry rooms where relative humidity max. 70% (at +20
to +40
C. Units should be protected from dust, dirt and water.
o
Avoid long term storaging. Longer than 1 year is not recommended.
3. DESCRIPTION
Cooling coils are used for air cooling in ventilation systems.
The coil consists of copper tubes and aluminium fins. The casing is made of galvanized sheet steel.
Water type coolers use coolant - cold water. Freon type coolers use the R410A freon.
Easy to mount.
Suitable for operation indoor environment.
The purpose of the unit is: cooling of clean air. The unit is used in clean air ventilation and conditioning systems.

4. SAFETY PRECAUTIONS

Do not use the unit for purposes other than its' intended use.
Do not disassemble or modify the unit in any way. Doing so may lead to mechanical failure or injury.
Use special clothing and be careful while performing maintenance, and repair jobs - edges of the components' casings may be sharp and cutting.
Do not place or operate unit on unsteady surfaces and mounting frames.
Mount the unit firmly to ensure safe operating.
Never use this unit in any explosive or aggressive elements containing environment.
5. MOUNTING
Installing should only be performed by qualified and trained staff.
Coils are designed for mounting in horizontal position.
Water connection process should be processed using mounting scheme (see the scheme S1).
S1:
a - water flow out;
b - air flow;
c - water flow in.
When cooler is already mounted the draining system has to be connected. In order to do that siphon must be screwed to the cooler draining
exhaust.
The draining system should be filled up with at least 0,5 l of water (siphon must be always filled with water).
Check if water reaches sewerage system.
When installed, the cooler should have an angle of 0-3
2
| EN
1
3
Product name
AS THE HEAT EXCHANGER IS NOT ENTIRELY
DRAINABLE, MAKE SURE THAT IT IS FILLED WITH
A SUITABLE ANTIFREEZING MIXTURE IN CASE
OFFREEZING RISK.
4
Weight
00,00 kg
6
Made in Šiauliai, Lithuania
Figure 1.1 - Technical label
(fig. S2).
o
2
SKU000000
5
LN: gu634612
2019.01.01
C), ambient temperature is within the range of +5
o
AVA/AVA DX/RWC/RFC v2019.04
C
o

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis