LSA 60TUR
9
Performance / coefficient of performance (COP)
9.1
Heat output / coefficient of performance (COP)
9.2
Heat output / coefficient of performance (COP)
^
9.3
Cooling capacity / coefficient of performance (COP)
9.4
Heat output / coefficient of performance (COP)
1. For air temperatures between -20 °C and 0 °C, flow temperatures increasing from 50 °C to 60 °C (see operating limit diagram)
2. The values specified apply when using the hydraulic 4-way reversing valve, available as an option (observe instructions for accessories).
The cooling capacities are reduced by approximately 10%, and the COPs by approximately 12%, when the 4-way reversing valve is not used.
If the 4-way reversing valve is not used, the minimum achievable cooling water flow temperature is increased by up to 3K.
3. In 2-compressor operation with A35/W18, results in a cooling water temperature difference of 5K ±1K.
4. The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation with a flow temperature of 35 °C.
The specified sound pressure level represents the free sound area level. The measured value can deviate by up to 16 dB(A) depending on the installation location.
5. Note that additional space is required for pipe connections, operation and maintenance
6. These data indicate the size and capacity of the system according to EN 14511. For an analysis of the economic and energy efficiency of the system, the bivalence point and
the regulation should be taken into consideration. These figures are only achieved with clean heat exchangers. Instructions for maintenance, commissioning and operation can
be found in the relevant sections of the assembly and operating instructions. The specified values have the following meaning, e.g. A 7 / W35: heat source temperature 7 °C and
heating water flow temperature 35 °C.
7. see CE declaration of conformity
8. The heat circulating pump and the heat pump manager must always be ready for operation.
EN-11
6
heat source/ heat sink
Air / water
performance level
at A-7 / W35
kW / ---
at A2 / W35
kW / ---
at A7 / W35
kW / ---
at A7 / W40-30
kW / ---
at A7 / W45
kW / ---
at A10 / W35
kW / ---
at A12 / W40-30
kW / ---
6
heat source/ heat sink
Brine / water
performance level
at B15 / W40-30
kW 7 ---
6 2
heat sink / heat source
Air / water
performance level
at A27 / W9
kW / ---
at A27 / W7
kW / ---
at A27 / W6
kW / ---
at A27 / W18
kW / ---
at A35 / W9
kW / ---
at A35 / W7
kW / ---
at A35 / W18
kW / ---
6
heat source / heat sink
Air & brine / water
performance level
at A-7 & B10 / W40-30
kW / kW / ---
at A2 & B10 / W40-30
kW / kW / ---
at A7 & B10 / W40-30
kW / kW / ---
452167.66.02 · FD 9509
EN 14511
1
2
20.4 / 2.8
39.7 / 3.0
26.4 / 3.5
47.6 / 3.4
34.1 / 4.2
55.3 / 3.8
32.9 / 4.1
57.8 / 3.7
31.7 / 3.5
54.9 / 3.3
37.0 / 4.5
59.6 / 4.0
36.5 / 4.3
63.6 / 4.0
1
2
43.7 / 5.1
79.4 / 4.9
EN 14511
1
2
54.5 / 2.8
27.1 / 3.0
27.0 / 2.9
54.0 / 2.7
41.8 / 4.0
72.7 / 3.4
49.0 / 2.3
24.0 / 2.4
36.0 / 3.2
65.8 / 2.8
1
2
22.6 / 2.9
49.0 / 3.3
34.1/ 4.1
59.5 / 3.8
36.4 / 4.3
66.6 / 4.1
www.glendimplex.de