Communication
Power supply
Current absorbed by BUS
BUS cable
Command elements
Inputs
Visualisation elements
Measuring elements
Temperature adjustment range
Usage environment
Operating temperature
Storage temperature
Relative humidity
Connection to the BUS
Electric connections
Degree of protection
Size
Standard references
Certifications
TECHNICAL DATA
TECHNICAL DATA
KNX BUS
via KNX BUS, 29 V DC SELV
5 mA
KNX TP1
1 miniature button key for programming the physical address
1 input for potential-free contact
(max. cable length 10m)
1 input for external temperature sensor
(e.g. GW 10 800)
(type NTC 10K)
1 front signalling LED
1 red LED for programming the physical address
1 internal sensor
adjustment range: 5 °C .. +40 °C
measurement range: 0 °C .. +60 °C
measurement resolution: 0,1 °C
measurement accuracy: ±0,5 °C between
+10 °C and +30 °C
T anti-freeze: +2 - +7 °C
T high temperature protection: +30 - +40 °C
Other Setpoints: +5 - +40 °C
Dry, indoor places
-5 - +45 °C
-25 - +70 °C
Max. 93% (non-condensative)
Coupling terminal, 2 pins, Ø 1 mm
Screw terminals - max. cable section: 2,5 mm²
IP20
1 Chorus module
Low Voltage Directive 2006/95/EC
Electromagnetic Compatibility Directive
2004/108/EC, EN50090-2-2, EN50428
KNX
18