STYLE 4462 RAMPAGE NOZZLE w/ Electric Pattern Actuator
The following is intended to provide the basic instructions for operating a Style 4462 Rampage Nozzle with Electric Pattern Actuator .
Read and understand these operating instructions before use .
PRODUCT RATINGS
Flow:
Maximum Pressure:
Minimum Voltage at motor:
Maximum Motor Current
Draw:
PRODUCT WARNINGS
WARNING:
Charge all lines slowly to facilitate a controlled water pressure build-up during start-up . Open and close
slowly . Rapid opening will produce a sudden thrust . Rapid opening and closing can cause water hammer .
Have your monitor properly supported to control the reaction force created by the stream .
WARNING:
At pressures below that indicated on the label, the nozzle will have reduced flow and reach . Be sure you have
enough flow and pressure for the situation (See IFSTA and NFPA manuals for guidelines) .
WARNING:
Ensure the nozzle is aimed in a direction that is safe, prior to flowing .
WARNING:
Do not use the nozzle as a forcible entry tool . Doing so may damage it or make it inoperable .
WARNING:
Ensure the thread on the nozzle swivel is matched to the thread on the monitor .
PRODUCT CAUTIONS
CAUTION:
If any tags or bands on the nozzle are worn or damaged and cannot be easily read, they should be replaced .
CAUTION:
For use with fresh water or standard fire fighting foams only . Not recommended for use with salt water .
After use with foam or salt water, flush with fresh water .
CAUTION:
Do not over tighten the nozzle onto the monitor .
CAUTION:
The nozzle is configured for optimum performance . Do not alter in any manner .
CAUTION:
Your nozzle should be inspected prior and after each use, to ensure it is in good operating condition .
Periodically, an unanticipated incident may occur where the nozzle is used in a manner that is inconsistent
with standard operating practices and those listed in IFSTA . A partial list of potential misuses follows:
OPERATING INSTRUCTIONS
500 -1000 gpm @ 100 psi/7 bar
200 psi/14 bar
12 Volt Motor: 10 Volts at 15 amps
24 Volt Motor: 20 Volts at 7 . 5 amps
12 Volt Motor: 3 amps
24 Volt Motor: 1 . 5 amps
120866