GEZE MERKUR S Montageanleitung Seite 11

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Configuration of individual parameters
Key
Parameter
code
C
Enhanced functions
Direction recognition
B
+
Mounting height
F
4
+
F
8
Field geometry
Field size
D
+
Relay hold interval
F
1
+
SMD function
F
3
+
SMD field size
F
7
CTM
+
F
5
(cross traffic
masking)
Filter for
interference sup-
+
F
6
pression
5.2.7
Explanation of individual parameters
Field size
/ field geometry
D
Depending on the field geometry (wide/narrow field), the field size can be set
correspondingly.
Narrow field:
T
B
Min. 0.7 x 0.6 m (WxD)
Max. 2.7 x 1.9 m (WxD)
Specified values measured with mounting height 2.2 m and inclination angle 35°.
Note:
The minimum field depth must be 1.5 m according to the guideline (AutSchR).
099582, 70705-9-9506 Ä-St. 7
Level Short description
Predefined settings for standard
1*- 6
applications (see table)
1
Off
2
Backwards
3*
Forwards
1
High (3-4 m)
2*
Standard (up to 3 m)
1
Narrow field
2*
Wide field
1 - 3
Small
4 - 6*
Medium
7 - 9
Large
1
0.2 s
2
0.5 s
Short
3
0.8 s
4*
1.0 s
5
1.5 s
Medium
6
2.0 s
7
2.5 s
8
3.0 s
Long
9
4.0 s
Off
1*
2
0.5 s
3
1.0 s
Decreasing sensitivity
4
1.5 s
5
2.0 s
6
0.5 s
7
1.0 s
Constant sensitivity
8
1.5 s
9
2.0 s
(plus SMD+)
1*- 3
Small
4 - 6
Medium
7 - 9
Large
1
Off
2*- 3
Low
4 - 6
Medium
7 - 9
High
On
Prevention of possible
1
spurious tripping by fluorescent
tubes
2*
Off
+
F
8
Wide field:
B
Min. 1.1 x 0.6 m (WxD)
Max. 4.7 x 1.7 m (WxD)
Montageanleitung Merkur S
SMD function
F
SMD = Slow motion detection:
The slightest (quasi-static) movements are detected as soon as the sensor is acti-
vated. Only when no more movements are registered during the set monitoring
period does the sensor relay the corresponding signal to the door controller. The
sensitivity during this this monitoring period can be set to decreasing or
constant.
SMD+:
Triggers the sensor when very slow movements occur. In this way, even objects
cm
< 5
(35° inclination angle) that are not detected with the normal detection
s
area are reliably identified (retirement home setting). In order to prevent the
door from being kept open too long, the SMD+ field is approximately half as
large as the detection area.
SMD field size
F
The SMD field sizes approximately correspond to those of the detection area,
+
+
~
i.e.
F
7
5
~
D
Cross traffic masking CTM
The CTM prevents a door from being inadvertently opened by people who only
walk past it but do not want to enter.
F
Optimum sensor settings:
- Narrow field
- Inclination angle of 30°-45°
5.2.8
Status query with remote control
The status query is to find out what parameters have been set. For this to take
place, the connection to the sensor has to be established and the correspon-
ding key code has to be entered. Next, a numerical key lights up that indicates
T
the respective parameter level.
+
and SMD+
3
1 . . . 9
3
+
7
+
5
+
F
5
5
1
9
F
5
1
9
* Factory setting
11