4.3 Connection of the Ethernet
cable
The Ethernet cable shield must always be
earthed via the connector. Always use a
shielded RJ45 connector.
The operations described in this chapter
can only be performed in the IP versions of
the product.
An Ethernet cable is included in the multi-polar cable
with the following characteristics: STP (shielded),
Category 5E.
Carry out the connections as described in the table
(according to the standard specifications: TIA/EIA-
568-B).

CONNECTION OF THE ETHERNET CABLE

Pin number
Cable color
1
Orange-White
2
Orange
3
Green-White
4
Blue
5
Blue-White
6
Green
7
Brown-White
8
Brown
Tab. 2
The example below shows a typical installation.
Personal
Computer
Fig. 1
Document 800-23092 Rev. A

4.4 Signal cable connection

SIGNAL CABLE CONNECTION
Colour
Pink
Violet (blue, cable
tail version)
Red (brown, cable
tail version)
Green
Grey
White
Yellow
Tab. 3

4.4.1 Relays connection

Due to the absence of polarity, both terminals of
the same relay can be used equally with either
alternating or continuous current.
Switch
CAUTION! TNV-1 installation type. The
installation is type TNV-1, do not connect it
to SELV circuits.
Function
Relay 1, Terminal A
Relay 1, Terminal B
Reset, factory reset
GND/Common
Not used
Not used
Not used
The external relay and alarm cable shield
must be earthed.
The relays are usable with the specifications
described below. Working voltage: up
to 30Vac or 60Vdc. Current: 1A max. Use
suitable cable sections with the following
characteristics: from 0.25mm² (23AWG) up
to 1.5mm² (16AWG).