4. CONTROL BOX CB230
4.1. DIMENSIONS CONTROL BOX CB230
4.2. REMOTE CONTROL OF MOTORIZED VALVES MIIF
When using remote controlled motorized valves, the 24V AC to the MIIF vacuum/ pressure
gauge box shall be taken from terminals X1/121 and X1/122. This will prevent the attention of
the valves when the web cleaner is not in operation.
Connect the 24V AC supply to terminals X3/103 and X4/104 in the MIIF cabinet.
Please refer to circuit diagrams as listened below.
4.3. EXTERNAL SIGNALS OF CONTROL BOX CB230
For CleanION web cleaner CB230-type control box, the following applies. Please refer to the
Drawings and circuit diagrams.
Alternative remote control of the start and stop of the fan unit. Remove the jumper between
terminals X1/109 and X1/110 and connect a normally closed relay in this position. Connect a
normally open relay between terminals X1/107 and X1/108. To start the fan. Close the relay
between X1/107 and X1/108 momentary (for 0,5sec.). To stop the fan, open the relay
between X1/109 and X1/110 momentary (for 0,5sec.).
Alternative remote control of the start and stop of the fan unit. Remove the jumper between
terminals X1/109 and X1/110 and connect between terminals X1/107 and X1/108 over a
remote relay, which can be controlled by a PC or the machine. When the terminals have
contact, the fan will start. Control voltage over the terminals is 24V AC.
CB_UM_9752435013_D_GB_F_V1_0
GB
19