Herunterladen Inhalt Inhalt Diese Seite drucken

Description Of The Unit; Operating Limits - aerme VEC Bedienungs Und Installationsanleitung Handbuch

Gebläsekonvektor
Inhaltsverzeichnis

Werbung

DESCRIPTION OF THE UNIT

The fan coil is a room air treatment terminal unit for mainly summer operation.
Install the unit on the suspended ceiling.
AVAILABLE VERSIONS AND SIZES
VEC fan coils are available in:
4 sizes with a 3-row coil
VEC 20
VEC 30
VEC 40
VEC 50

OPERATING LIMITS

Maximum water input temperature ........................... 50°C
Maximum operating pressure ..................................... 8 bar
Operating voltage ..............................230V(±10%) ~ 50Hz
Room temperature .................................................. 0-40°C
Air humidity ..................................................... <85% U.R.
Output limits (3-row coil):
MOD.
VEC
Minimum output
[l/h]
Maximum output
[l/h]
Water temperature
In order to prevent air stratification
in the room, and therefore to achieve
improved mixing, it is obligatory not
to supply the fan coil with water at a
Minimum average water temperature
If the fan coil is working in cold
continuous mode inside an environment
where the relative humidity is high,
condensate might form on the air
delivery. This condensate might be
deposited on any objects underneath
and on the floor.
To avoid condensate on the external
structure of the device while the fan is
MINIMUM AVERAGE WATER TEMPERATURE
Temperature of the air in the room
with wet bulb °C
20
30
40
100
100
150
750
750
1100
temperature over 50°C.
The use of water at high temperatures
could cause squeaking due to the
different thermal expansions of the
functioning, the average temperature of
the water must not be lower than the
limits shown in the table below, that
depend on the thermo-hygrometric con-
ditions of the air in the room.
The limits mentioned above refer to
operation while the fan is set
to its minimum speed level.
In the event of prolonged fan inactivity
Temperature of the air in the room with dry bulb °C
21
23
15
3
3
17
3
3
19
3
3
21
6
5
23
-
8
compulsory accessory
VEC 20 GL
VEC 30 GL
VEC 40 GL
VEC 40 GL
VEC 20
VEC 20 GL
50
150
1100
elements (plastic and metal), this does
not however cause damage to the unit if
the maximum operating temperature is
not exceeded.
and with cold water passing through the
coil, condensate may form on the exter-
nal case of the unit. As a result, we rec-
ommend including the three-way valve
accessory.
25
27
3
3
3
3
3
3
4
3
7
6
IVECLJ 1009 - 5074550_04
29
31
3
3
3
3
3
3
3
3
5
5
11

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis