Ground Your Chassis

To properly ground your I/O chassis:
verify grounding configuration
install a central ground bus
connect equipment grounding conductor
connect equipment grounding conductor to ground bus
connect ground bus to grounding-electrode system
Verify Grounding Configuration
This figure shows you how to run ground connections from the chassis to the
ground bus. Two acceptable grounding methods are shown; we recommend using a
ground bus because it reduces the electrical resistance at the connection.
2
2 mm
(14 AWG)
2
2 mm
(14 AWG)
2
2 mm
(14 AWG)
10 AWG
SLC 500™ Modular Chassis
See page:
9
10
10
11
11
Earth Ground
2
5.2 mm
(10 AWG)
Keep wire length as
short as possible.
Preferred Grounding Method.
Publication 1746-IN016A-MU-P
9