Display Readout On 884501 Of Sensor Error Detection And Input Signal Outside Range - Morsettitalia 884114 Bedienungsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

TC input:
Min.
Type
value
B
0°C
+1820°C
E
-100°C
+1000°C
J
-100°C
+1200°C
K
-180°C
+1372°C
L
-200°C
+900°C
N
-180°C
+1300°C
R
-50°C
+1760°C
S
-50°C
+1760°C
T
-200°C
+400°C
U
-200°C
+600°C
W3
0°C
+2300°C
W5
0°C
+2300°C
LR
-200°C
+800°C
Cold junction compensation (CJC)
CJC via external sensor in
connector 5910 ......................................... 20...28°C ≤ ±1°C
CJC via internal sensor ........................... ±(2.0°C + 0.4°C * Δt)
Δt = internal temperature - ambient temperature
Sensor error detection, all TC types ........... Yes
Sensor error current:
when detecting ....................................... Nom. 2 µA
else .......................................................... 0 µA
Current input:
Measurement range .................................... 0...20 mA
Programmable measurement ranges .......... 0...20 and 4...20 mA
Input resistance ........................................... Nom. 20 Ω + PTC 50 Ω
Sensor error detection:
Loop break 4...20 mA.............................. Yes
voltage input:
Measurement range .................................... 0...12 VDC
Programmable measurement ranges .......... 0...1 / 0.2...1 / 0...5 / 1...5 /
Input resistance ........................................... Nom. 10 MΩ
Current output:
Signal range (span) ...................................... 0...20 mA
Programmable signal ranges ...................... 0...20 / 4...20 / 20...0 / 20...4 mA
36
Max.
value
Standard
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
IEC 60584-1
IEC 60584-1
IEC 60584-1
IEC 60584-1
DIN 43710
ASTM E988-90
ASTM E988-90
GOST 3044-84
-20...20°C and 28...70°C ≤ ±2°C
0...10 and 2...10 VDC
Load (max.) .................................................. 20 mA / 800 Ω / 16 VDC
Load stability ............................................... ≤ 0.01% of span / 100 Ω
Sensor error detection ................................ 0 / 3.5 / 23 mA / none
NAMUR NE 43 Upscale / Downscale ......... 23 mA / 3.5 mA
Output limitation:
on 4...20 and 20...4 mA signals .............. 3.8...20.5 mA
on 0...20 and 20...0 mA signals .............. 0...20.5 mA
Current limit ................................................. ≤ 28 mA
voltage output:
Signal range ................................................ 0...10 VDC
Programmable signal ranges ...................... 0...1 / 0.2...1 / 0...10 / 0...5 / 1...5 /
Load (min.) ................................................... 500 kΩ
observed authority requirements:
EMC 2004/108/EC ...................................... EN 61326-1
LVD 2006/95/EC .......................................... EN 61010-1
UL, Standard for Safety .............................. UL 508
of span = of the currently selected measurement range
Display readout on the 884501 of sensor error detection and
input signal outside range
Sensor error check:
Device:
Configuration
OUT.ERR=NONE.
884114
Else:
Outside range readout (IN.LO, IN.HI):
If the valid range of the A/D converter or the polynomial is exceeded
Input
Range
0...1 V / 0.2...1 V
VOLT
0...10 V / 2...10 V
CURR
0...20 mA / 4...20 mA
Ω
0...800
LIN.R
0...10 kΩ
POTM
-
TEMP
TC / RTD
2...10 / 1...0 / 1...0.2 / 5...0 / 5...1 /
10...0 og 10...2 V
standard:
Sensor error detection:
OFF
ON
Readout
Limit
IN.LO
< -25 mV
IN.HI
> 1.2 V
IN.LO
< -25 mV
IN.HI
> 12 V
IN.LO
< -1.05 mA
IN.HI
> 25.05 mA
IN.LO
< 0 Ω
IN.HI
> 1075 Ω
IN.LO
< 0 Ω
IN.HI
< 110 kΩ
IN.LO
< -0.5 %
IN.HI
> 100.5 %
IN.LO
< temperature range -2°C
IN.HI
> temperature range +2°C
37