Filters
Check and clean or replace, if necessary, the filters in the line, pump and nozzle.
If there is rust or other impurities in the pump filter, use a separate pump to remove water and other
impurities from the bottom of the tank.
Fan
Check that dust is not accumulated inside the fan and on the rotor blades: this reduces the air flow and
causes, as a consequence, polluting combustion.
Combustion head
Check that all the parts of the combustion head are intact, not deformed by the high temperatures, free
of impurities from the surrounding environment, and correctly positioned.
Nozzles
Avoid cleaning the hole of the nozzles, so as to not damage them
Replace the nozzles every 2-3 years, or when necessary. Combustion must be checked when changing the
nozzle.
Photo cell
Clean the glass for dust. The photo cell is pushed into place; to remove it, simply pull it out.
Flexible pipes
Check that they are in good condition, that they have not been stepped on or deformed.
Tank
Every 5 years or so, remove the water from the bottom of the tank using a separate pump.
3.4 Troubleshooting
Problem
The burner does not ignite
During pre-ventilation, the
burner shuts down
The burner performs the pre-
ventilation and ignition cy-
cle, but there is no flame and
the burner shuts-down.
26
Possibile causes/ Recommended solution
No electrical power / Close the switches, check the fuses
Appliance shut-down/ Reset the appliance
Electrical devices defective/ Replace
Pump blocked/ Replace
Electric motor defective/ Replace
Electrical connections incorrect / Check
Photo cell short-circuited/ Replace the photo cell
External light strikes the photo cell/ Eliminate source of light
Electrical devices defective/ Replace
Oil valve defective/ Replace
No fuel in the tank, or water on the bottom/ Top up fuel or remove the water
Oil supply valve closed/ Open
Filters dirty (line – pump - nozzle)/ Clean
Pump not primed/ Prime and look for cause of loss of prime
Ignition electrodes poorly adjusted, or dirty/ Adjust or clean
Nozzle blocked, dirty or deformed/ Replace
Head and damper poorly adjusted/ Adjust
Electrodes defective or earthed/ Replace
Ignition transformer defective/ Replace
Electrode cables defective or earthed/ Replace
Electrode cables deformed due to high temperature/ Replace and protect
Electrical connections to the valve or transformer incorrect / Check
Defective appliance/ Replace
Motor-pump joint broken/ Replace
Pump inlet connected to the return pipe/ Correct the connection