Herunterladen Inhalt Inhalt Diese Seite drucken

Applications; Technical Characteristics; Mounting; Input - PR electronics 2222 Handbuch

Schaltmodus spannungsversorgung
Vorschau ausblenden Andere Handbücher für 2222:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

SWITCHMODE POWER SuPPLY 2222
• 230 or 115 VAC primary voltage
• 24 or 15 VDC output voltage
• Double isolation by 3.75 kVAC
• 48 Watt output power, short circuit-protected
• Thermal protection against overload
• DIN rail mounting on a standard 11-pole relay
socket

aPPLICaTIONS:

General 24 or 15 VDC supply for equipment that requires a stabilised DC voltage .
Separation of circuits in safety installations according to the PELV/SELV norm .
Two units can be connected in series to achieve a plus / minus supply or a higher
output voltage . The small mechanical dimensions of the switchmode power
supply allow for a high DC output power, even in narrow spaces .

TECHNICaL CHaRaCTERISTICS:

The power supply is based on primary switchmode technology to achieve a high
efficiency . Galvanic isolation between the primary and the secondary voltage is
achieved through the double-isolated safety transformer . A thermal fuse protects
the input circuit when the internal temperature exceeds 100°C .
An 1 A fuse on the input protects the switchmode power supply against a short
overload . The DC output is protected against a short circuit by an electronic
current limiter that activates at an output current of 2 .5 A . A green LED on the
front of the module indicates an active primary voltage .

MOuNTING:

To achieve maximum cooling of the module, mounting in a vertical position at a
distance of minimum 10 mm between neighbouring units is recommended .

INPuT:

AC power supply according to the specifications .

OuTPuT:

DC voltage of 24 or 15 V . An internally mounted potentiometer allows for a ±5%
adjustment of the output voltage .
18

ELECTRICaL SPECIFICaTIONS:

Specifications range:
-20°C to +60°C
Common specifications:
Max . consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 VA
Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≥ 80%
Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 A T / 250 VAC
Thermal overload protection . . . . . . . . . . . . . . . . . . . . . . 100°C
Isolation, test / operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 .75 kVAC / 250 VAC
Power derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1% / °C amb . (T amb . > 40°C)
Transient stability (10% - max . load) . . . . . . . . . . < 500 mV
Temperature coefficient . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 .05%/°C
Effect of supply voltage
change (±10%) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 1%
EMC immunity influence . . . . . . . . . . . . . . . . . . . . . . . . . . . . < ±0 .5%
Relative air humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 95% RH (non-cond .)
Dimensions (HxWxD)
(D is without pins) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 .5 x 35 .5 x 84 .5 mm
Protection degree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP30
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210 g
Input:
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207 . . .253 VAC
Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 . . .60 Hz
Output:
Output voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 or 15 VDC
Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ±5%
Output power (max .) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 W
Output current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 A / 24 VDC, 2 A / 15 VDC
Load stability (0 - max . load) . . . . . . . . . . . . . . . . . . . . . . < 1 .5% / A
Electronic current limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Nom . 2 .5 A
Output ripple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ≤ 40 mVRMS (100 kHz)
GOST R approval:
VNIIM, Cert. no. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . See www .prelectronics .com
Observed authority requirements:
EMC 2004/108/EC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . EN 61326-1
LVD 2006/95/EC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . EN 61010-1
PELV/SELV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IEC 364-4-41 and EN 60742
102 .4 . . .132 .2 VAC
Standard:
19