Quick Start-up of Omron RX Frequency Converter
Elektror Basic Parameterisation:
Parameter
Description
EN
b049
Operating mode (HD/ND mode)
A001
Selection of frequency setpoint source
A002
Selection of start command source
A004
Maximum frequency [Hz]
A003
Cut-off frequency [Hz]
A051
DC-braking
A054
DC-braking power
A082
Motor voltage [V]
b012
Current value of I²t monitoring [A]
b035
Direction of rotation
b083
Clock frequency [kHz]
b098
PTC input (terminal TH)
b099
PTC error threshold
H003
Motor rated power [kW]
H004
Number of poles on motor
F001
Output frequency - setpoint value [Hz]
F002
Output frequency - run-up time [s]
F003
Output frequency - elapsed time [s]
8
Elektror Standard
01: Normal Duty; ND; increased rated power
(low power reserve)
02: Control panel
02: Control panel
Rated frequency, see type plate
Rated frequency, see type plate
00: Off
0%
Rated voltage, see type plate
Rated current, see type plate
01: Forward
10 kHz
01: Active
3000 Ohm
Rated power, see type plate
2
0... max rated frequency, see type plate
10 s [longer for larger units]
20 s [longer for larger units]