Herunterladen Inhalt Inhalt Diese Seite drucken

Commissioning; Dip Switch Settings - Pepperl+Fuchs LAL-SRW Bedienungsanleitung

Vorschau ausblenden Andere Handbücher für LAL-SRW:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

WARNING DEVICE

Commissioning

4
Commissioning
4.1

DIP switch settings

Warning!
Do not make settings at the DIP switch with the voltage on
Injuries and damage to the device are possible when working with live parts.
Do not remove the side cover above the DIP switches as long as the device is connected
to the voltage supply.
Install the cover above the DIP switches before the device is connected to the voltage
supply.
Switch
DIP 1
NVF sensor (NVF-
104/34-PF)
DIP 2
KVF sensor (KVF-104-
PF) or SLU sensor (SLU-
103-**)
DIP 3
Acoustic alarm
DIP 4
Relay setting
DIP 5
DIP 4
Relay setting
DIP 5
DIP 4
Relay setting
DIP 5
DIP 4
Relay setting
DIP 5
DIP 6
Repeat alarm setting in
24 hours
Description
ON
connected
OFF
not connected
ON
connected
OFF
not connected
ON
Acoustic alarm switched on.
OFF
Acoustic alarm switched off.
ON
Relays 1 and 2 switch in all alarm states. If an
alarm event is no longer pending, relay 1
ON
switches back automatically AND relay 2
remains unchanged until the alarm has been
acknowledged by actuating "ALARM RESET".
This shows therefore that an alarm was
present.
ON
Relays 1 and 2 switch in alarm states. After 3
minutes, relay 2 switches back (even if an alarm
OFF
state is pending). If the alarm state disappears,
relay 1 and/or relay 2 switches again. (If
"ALARM RESET" is actuated, the relays switch
again)
OFF
Relay 1 switches with alarm state at NVF
sensor; relay 2 switches with alarm state at KVF
ON
sensor. If the alarm state disappears, relays 1
and/or 2 switch again (if "ALARM RESET" is
actuated, the relays switch again).
OFF
Relays 1 and 2 switch in alarm states
irrespective of which sensor. If the alarm state
OFF
disappears, relays 1 and/or 2 switch again (if
"ALARM RESET" is actuated, the relays switch
again).
ON
Repeat alarm setting switched on. This also
applies to the function of relays 1 and 2.
OFF
Repeat alarm setting switched off
EN
EN - 19

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis