pefra Alpha 2 Anleitung Seite 4

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

` Configuration of the base station with
room control unit Radio Display
CAUTION
Damage to the overall system
¾ Faulty configuration leads to errors and installati-
on damage.
The Service level of the base station Radio Display is
protected with a PIN code and may only be used by
authorized specialists.
¾ Press the rotary control.
¾ Select the menu "Service Level" and activate by
pressing.
¾ Enter the 4-digit PIN (standard: 1234) by rotating
and pressing.
¾ Select parameters (PAr) by pressing again and en-
ter the number code of the desired parameter (see
following table).
¾ Change parameters as required and confirm by
pressing.
PAr Description
Unit
010 Setting the heating sys-
FBH St.=0
tem Floor heating (FBH)
FBH NE=1
standard / FBH low ener-
RAD=2
gy / radiator / convector
KON pas.=3
passive / convector active
KON act.=4
020 Blocking the switching
normal=0
outputs depending on
Block heating=1
the activated operating
Block cooling=2
mode (heating/cooling)
030 Unlocking the operating
Deactivated=0
lock (child safety lock)
Activated=1
031 Set PIN for operating lock
0000..9999
if par. 30 is activated
040 Logging on an additional
no sensor=0
sensor, connected to the
dew point sen-
room control unit, for the
sor=1
registration of the floor
floor heating
temperature (FBH), the
temp=2
room temperature or the
room temp=3
dew point
060 Registration of the actual
-2.0...+2.0 K
temperature with a cor-
in increments of
rection factor
0.1
110 global change-over of the
NC=0
control direction of the
NO=1
switching output for NC
and NO actuators
120 Toggle function of the
°C=0
temperature display bet-
°F=1
ween degree Celsius and
degree Fahrenheit
130 Use the control of a local
local=0
recirculation pump (in the
global=1
heating circuit distribu-
tor) or a global recircula-
tion pump (heating instal-
lation).
131 Selection of the used
CP=0
pump:
Conventional
HP=1
Pump (KP) / High efficien-
cy Pump (HP)
132 Time elapsing from the
[min]
moment of the command
from a switching output
until the pump is actually
switched on.
PAr Description
Unit
133 Time from the moment
[min]
of switching off the swit-
ching outputs until the
pump is actually switched
off.
134 The control direction can
normal=0
be inverted if the pump
inverted=1
relay is used as control
output
135 The minimum running
[min]
time indicates how long
the HP must run until
it may be switched off
again.
136 High efficiency pump:
[min]
The pump may only be
switched off if a mini-
mum standstill time can
be ensured.
160 Setting
the
antifreeze
Deactivated=0
function of the switching
Activated=1
output
161 Setting the antifreeze li-
[°C]
mit value
170 Smart
Start
function:
Deactivated=0
Teaching-in the tempera-
Activated=1
ture behaviour of the he-
ating zone
180 Duration until activation
[min]
of emergency operation
181 Duration of a PWM cycle
[min]
in emergency operation
182 Activation duration of the
[%]
PWM in heating mode
during emergency ope-
ration
183 Activation duration of the
[%]
PWM in cooling mode
during emergency ope-
ration
190 Duration until the activa-
[d]
tion of the valve protecti-
on function after the last
trigger
191 Valve activation duration
[min]
when valve protection
Deactivated =0
function is active
210 Setting the First Open
[min]
function (FO) for activa-
off = 0
tion of all switching out-
puts at power-up
220 Automatic switching bet-
Deactivated=0
ween summer and winter
Activated=1
time according to CET
` Configuration of the base station with the
microSD card
WARNING
Danger to life due to the electrical voltage
at the base station
¾ Only authorised specialists may perform the sys-
tem configuration via microSD card.
¾ Always disconnect from the mains network and
secure against unintended activation before
opening the base station.
The configuration of the base station is done via the
Service level of the room control unit Radio Display.
If no room control unit Radio Display is available,
configuration can alternatively be performed with a
microSD card. Only authorised specialists may per-
form this type of configuration.
Individual settings can be made via the EZR Manager
SD Card under www.ezr-home.de and transferred to
the base station via the microSD card. The base sta-
tion can read microSD cards with the formats FAT16
and FAT32.
CAUTION
Damage of the base station caused by im-
proper handling
¾ Never separate the base station from the mains
during the boot process
¾ Never remove the SD card from the unit before
the end of the boot process.
¾ Open www.ezr-home.de via the web browser of
a PC, select the menu item EZR Manager SD Card
and follow the instructions.
¾ Separate the base station from the mains voltage
and open it, see also "Installation".
¾ Insert the MicroSD card with the updated data
into the base station.
¾ Close the base station and apply mains voltage.
9 The base station restarts and the update process
starts automatically.
` Valve protection function
During periods without valve activation (e. g. outside
the heating period) the heating zone with logged-in
room control unit is activated in a cyclic way in order
to avoid a clogging of the valve.
` Antifreeze protection
Independent from the operating mode, the swit-
ching output is equipped with an antifreeze function.
As soon as a previously set antifreeze temperature
(5...10°C) is fallen short of, the valve of the allocated
heating zone is activated until this temperature is re-
ached. The antifreeze temperature can be set via the
service level of the RBG display or via the microSD
card (parameter 161).
` Emergency operation
If the base station is unable to establish a radio
connection to the room control unit after a set time
has elapsed, emergency operation is activated auto-
matically. In emergency operation, the switching out-
puts at the base station are activated with a modified
PWM cycle duration (parameter 181) independent
from the heating system in order to avoid complete
cooling of the rooms (in heating operation) or dewing
(in cooling operation).
` Resetting the factory settings
WARNING
Danger to life due to the electrical voltage
at the base station
¾ Only authorised specialists may open the base sta-
tion.
¾ Always disconnect from the mains network and
secure against unintended activation before
opening the base station.
¾ If present, remove the MicroSD Card from the
base station and delete the parameter file "pa-
rams_usr.bin" at the PC.
¾ Press the rmBUS key of the base station for three
seconds in order to start the pairing mode.
9 The LED "rmBUS" flashes.
¾ Press the rmBUS push-button again for a duration
of 10 seconds.
9 A restart will be performed.
9 Now the base station is reset to factory settings
and behaves as it did during the first commissi-
oning.
Note:
• All user settings will be lost.
• A previously allocated room control unit must
be paired newly.
` Error indication and elimination of errors
LED signalling
Meaning
Heating zone
Radio connection to the
Duration in seconds
room control unit faulty:
0
1
2
3
4
• Change the position of
the room control unit or
use a repeater or an acti-
ve antenna.
Heating zone
Low battery capacity of
Duration in seconds
the room control unit:
0
1
2
3
4
• Change the batteries in
the room control unit
Heating zone
Emergency operation ac-
Duration in seconds
tive:
0
1
2
3
4
• Change the batteries in
the room control unit
• Perform a radio test
• If necessary, reposition
the room control unit.
• Replace a defective room
control unit
` Cleaning
Only use a dry and solvent-free, soft cloth for clea-
ning.
` Decommissioning
WARNING
Danger to life due to the electrical voltage
at the base station
¾ Always disconnect from the mains network and
secure against unintended activation before
opening it.
¾ Disconnect external voltages and secure against
unintended activation.
¾ Pull the mains plug and and disconnect the entire
installation.
¾ Remove the wiring to all externally connected
components as e. g. CO input/output and actu-
ator.
¾ Uninstall the device and dispose of properly.
` Disposal
The base station must not be disposed with
domestic waste. The operator has the duty
to hand the device to appropriate collection
points. The separate collection and orderly
disposal of all materials will help to conserve
natural resources and ensure a recycling in a
manner that protects human health and the
environment. If you need information about
collection points for your devices, please cont-
act your local municipality or your local waste
disposal services.
` Technical data
Number of heating
1
zones
Number of actuators
1
Max. nominal load of
10 W
actuator
Switching power
max. 1 A
Operating voltage
230 V / ±10% / 50 Hz
Mains connection
NYM connection terminals 2 x 1.5 mm²
Power consumption
<11 W
(without pump)
Power consumption
<1 W
in idle operation
Protection class
II
Degree of protection
IP20
Overvoltage category
II
Environment tempe-
0 °C to +60 °C
rature
Storage temperature
-25 °C to +70 °C
Humidity
5 to 80%, not condensing
Dimensions
86 x 86 x 33
Material
ABS
Colour
RAL9010 (pure white)
Weight
120 g
Controlling precision
±1 K
of the target value:
Hunting
±0,2 K
Modulation
FSK
Carrier frequency
868 MHz, bidirectional
Range
25 m in buildings / 250 m in open air
Radiated power
max. 10 mW
These instructions are protected by copyright. All
rights reserved. It may not be copied, reproduced,
abbreviated or transmitted, neither in whole nor in
parts, in any form, neither mechanically nor electro-
nically, without the previous consent of the manu-
facturer.
© 2014
Made in Germany
130639.1439